Wiring Device-Kellems Full Product Catalog

H SECTION

PIN AND SLEEVE DEVICES/MECHANICAL INTERLOCKS

Style II Insulgrip® Mechanical Interlocks Specifications

Specifications

Materials

Typical Specifications Manufacturer’s Identification Description Electrical Type Rating Configuration Enclosure Type (UL 50E)

Part

Material

Hubbell HBL460MIFS2W Fused Insulgrip® Pin and Sleeve Mechanical Interlock 3 Pole + Earth 60A, 250VDC/600VAC Per UL 1686 C1 Indoor & Outdoor - 4X (Watertight, Washdown) Indoor - 12 (Dust Tight, Falling Dirt) IP66 Suitability UL Listed for US and Canada

Base, Door and Handle Conduit Hub Enclosure Gasket and Shaft Seal Shaft and Mounting Inserts Ground Plate Enclosure Screws and Hinge Spring Hinge Pin Contact Carrier

PBT Zinc, 30A – 1 in., 60A – 1-1/4 in. NPT Neoprene

Brass Galvanized Steel Stainless Steel

Nickel-Plated Brass Thermoset Polyester

Ingress Protection Certification

Note: This device provides fused switched control of a plug connected load and includes an interlocking feature to prevent the plug from being disconnected or the door from opening while the receptacle is energized. The switch cannot be turned on until the plug is fully inserted.. Performance Electrical Dielectric Voltage

Withstands 3,000VAC Min. 250VDC/600VAC. Certified for current interrupting at full rated current and voltage. Suitable for use on a circuit capable of delivering not more than 200,000 RMS symmetrical amperes at the voltage rating of receptacle.

Max. Working Voltage Current Interrupting Short Circuit Withstand Rating

Operations

Mechanical 10,000 cycles minimum.

Mechanical Impact Resistance Terminal Identification Product Ratings Mounting Environmental Moisture Resistance Ingress Protection Flammability Operating Temperatures

In accordance with UL 746C. In accordance with UL, CSA and international conventions. Ratings are part of the external label and molded into the receptacle housing. External adjustment feet.

Indoor & Outdoor - 4X (Watertight, Washdown); Indoor - 12 (Dust-tight, Falling dirt). IP66 Suitability. UL94-5VA and V-0 Classification. Max. Continuous +60°C; Min. Continuous -40°C w/o impact. All exposed insulating materials are UV stabilized. UL Listed Class “J”. CSA Certified HRCI-J.

UV Resistance Fuse Types

Horsepower Ratings 30A Horsepower Ratings

60A Horsepower Ratings

3 Phase A.C.

Standard

Maximum*

3 Phase A.C.

Standard

Maximum*

200-240V 480V 600V

3 5 7.5

7.5 15 20

200-240V 480V 600V

7.5 15 15

15 30 50

Dimensions

10.18" (258.6)

7.27" (184.7)

9.31" (236.5)

1.51" (38.4) 30A 1.68" (42.7) 60A

7.19" (182.6)

3.60" (91.4)

11.46" (291.6)

12.37" (314.2)

15.03" (381.8)

14.48" (367.8)

15.36" (390.1)

4.00" (101.6) 30A 5.00" (127.0) 60A

8.43" (214.1)

Note: 30A – 1 inch NPT hub supplied; 60A – 1-1/4 inch hub supplied.

Dimensions in Inches (mm)