Wiring Device-Kellems Full Product Catalog
H SECTION
PIN AND SLEEVE DEVICES/MECHANICAL INTERLOCKS
Style II Insulgrip® Mechanical Interlocks Specifications
Specifications
Materials
Typical Specifications Manufacturer’s Identification Description Electrical Type Rating Configuration Enclosure Type (UL 50E)
Part
Material
Hubbell HBL460MIFS2W Fused Insulgrip® Pin and Sleeve Mechanical Interlock 3 Pole + Earth 60A, 250VDC/600VAC Per UL 1686 C1 Indoor & Outdoor - 4X (Watertight, Washdown) Indoor - 12 (Dust Tight, Falling Dirt) IP66 Suitability UL Listed for US and Canada
Base, Door and Handle Conduit Hub Enclosure Gasket and Shaft Seal Shaft and Mounting Inserts Ground Plate Enclosure Screws and Hinge Spring Hinge Pin Contact Carrier
PBT Zinc, 30A – 1 in., 60A – 1-1/4 in. NPT Neoprene
Brass Galvanized Steel Stainless Steel
Nickel-Plated Brass Thermoset Polyester
Ingress Protection Certification
Note: This device provides fused switched control of a plug connected load and includes an interlocking feature to prevent the plug from being disconnected or the door from opening while the receptacle is energized. The switch cannot be turned on until the plug is fully inserted.. Performance Electrical Dielectric Voltage
Withstands 3,000VAC Min. 250VDC/600VAC. Certified for current interrupting at full rated current and voltage. Suitable for use on a circuit capable of delivering not more than 200,000 RMS symmetrical amperes at the voltage rating of receptacle.
Max. Working Voltage Current Interrupting Short Circuit Withstand Rating
Operations
Mechanical 10,000 cycles minimum.
Mechanical Impact Resistance Terminal Identification Product Ratings Mounting Environmental Moisture Resistance Ingress Protection Flammability Operating Temperatures
In accordance with UL 746C. In accordance with UL, CSA and international conventions. Ratings are part of the external label and molded into the receptacle housing. External adjustment feet.
Indoor & Outdoor - 4X (Watertight, Washdown); Indoor - 12 (Dust-tight, Falling dirt). IP66 Suitability. UL94-5VA and V-0 Classification. Max. Continuous +60°C; Min. Continuous -40°C w/o impact. All exposed insulating materials are UV stabilized. UL Listed Class “J”. CSA Certified HRCI-J.
UV Resistance Fuse Types
Horsepower Ratings 30A Horsepower Ratings
60A Horsepower Ratings
3 Phase A.C.
Standard
Maximum*
3 Phase A.C.
Standard
Maximum*
200-240V 480V 600V
3 5 7.5
7.5 15 20
200-240V 480V 600V
7.5 15 15
15 30 50
Dimensions
10.18" (258.6)
7.27" (184.7)
9.31" (236.5)
1.51" (38.4) 30A 1.68" (42.7) 60A
7.19" (182.6)
3.60" (91.4)
11.46" (291.6)
12.37" (314.2)
15.03" (381.8)
14.48" (367.8)
15.36" (390.1)
4.00" (101.6) 30A 5.00" (127.0) 60A
8.43" (214.1)
Note: 30A – 1 inch NPT hub supplied; 60A – 1-1/4 inch hub supplied.
Dimensions in Inches (mm)
H-48 | www.hubbell.com/wiringdevice-kellems
Made with FlippingBook - Online Brochure Maker