Versa-Tech® Terminal Unit (10F)

2. Binary Output Status/Control Relay Output Points

Available in

Sl No

DNP3 Point

Description

VTI

VTII

May be mapped multiple times for any given phase. This is a placeholder for customer mapping purposes. It will always return '0'

Dummy

Yes

Yes

1

2

Trip Contacts

Trip Recloser Contacts

Yes

Yes

3

Contacts Close

Close Recloser Contacts

Yes

Yes

Trip Recloser Contacts and drop the Manual Handle (yellow). NOTE: Once SCADA Master issues this command there is no way of closing back the contacts remotely from SCADA Master

4

Lockout

•

Yes

5

Non-Reclose On

Enable Non-Reclose Mode

Yes

Yes

6

Non-Reclose Off

Disable Non-Reclose Mode

Yes

Yes

7

HLT On

Turn on HLT Function

Yes

Yes

8

HLT Off

Turn off HLT Function

Yes

Yes

9

Beacon Flash On

Flash Beacon for 1 minute

Yes

Yes

10

Beacon Flash Off

Turn off beacon flashing

•

Yes

Connect to Recloser

11

Establish connection with Recloser

Yes

Yes

Disconnect from Recloser

12

Disconnect from Recloser

Yes

Yes

Clear all temporary operation event counters ("This Count"), including 1-4th shot counters for the VTII.

Clear Resettable Operation Counters

13

Yes

Yes

Page 10F-5 | February 2014

Made with FlippingBook flipbook maker