Versa-Tech® Terminal Unit (10F)
DNP Points and Defaults
1. Binary Input Points
Available in
Sl No
DNP3 Point
Description
VTI
VTII
May be mapped multiple times for any given phase. This is a placeholder for customer mapping purposes. It will always return '0'
Dummy
Yes
Yes
1
Battery Voltage Status
2
0 - Good, 1 – Schedule to change
•
Yes
Status of Recloser Manual Handle (yellow), if in Lockout or not. 0 - Not in Lockout, 1 - Recloser is in Lockout State Status of the Recloser Contacts, if they are Tripped or Closed. 0 - Contact Tripped, 1 - Contact Closed Communication status with the recloser. 0 - Not connected, 1 - Connected to Recloser Recloser Assigned to VTU. 0 - Recloser not assigned, 1 - Recloser assigned Non-Reclose Mode Status 0 - NR Off, 1 - NR On Status of the Beacon Flashing. 0 - Beacon On, 1 - Beacon Off Status of INOW if below 15A or not. 0 - INOW >15A, 1 - INOW <=15A. This will be set whenever recloser sees a fault (includes Sequence Coordination events). This flag is cleared automatically when the VTU Successfully Reports this DNP point to the SCADA Master. Hot Line Status. 0 - HLT Off, 1 - HLT On
3
Lockout Status
•
Yes
Recloser Contacts Status
4
Yes
Yes
Recloser Connected Status
5
Yes
Yes
Recloser Configured Status
6
Yes
Yes
7
HLT Status
Yes
Yes
Non-Reclose Status Beacon Flash Status Current Less than 15A
8
Yes
Yes
9
•
Yes
10
Yes
Yes
11
Fault Detected
Yes
Yes
Page 10F-4 | February 2014