Versa-Tech® Terminal Unit (10F)
2. Binary Output Status/Control Relay Output Points
Available in
Sl No
DNP3 Point
Description
VTI
VTII
May be mapped multiple times for any given phase. This is a placeholder for customer mapping purposes. It will always return '0'
Dummy
Yes
Yes
1
2
Trip Contacts
Trip Recloser Contacts
Yes
Yes
3
Contacts Close
Close Recloser Contacts
Yes
Yes
Trip Recloser Contacts and drop the Manual Handle (yellow). NOTE: Once SCADA Master issues this command there is no way of closing back the contacts remotely from SCADA Master
4
Lockout
•
Yes
5
Non-Reclose On
Enable Non-Reclose Mode
Yes
Yes
6
Non-Reclose Off
Disable Non-Reclose Mode
Yes
Yes
7
HLT On
Turn on HLT Function
Yes
Yes
8
HLT Off
Turn off HLT Function
Yes
Yes
9
Beacon Flash On
Flash Beacon for 1 minute
Yes
Yes
10
Beacon Flash Off
Turn off beacon flashing
•
Yes
Connect to Recloser
11
Establish connection with Recloser
Yes
Yes
Disconnect from Recloser
12
Disconnect from Recloser
Yes
Yes
Clear all temporary operation event counters ("This Count"), including 1-4th shot counters for the VTII.
Clear Resettable Operation Counters
13
Yes
Yes
Page 10F-5 | February 2014
Made with FlippingBook flipbook maker