Versa-Tech® Terminal Unit (10F)

2. Binary Output Status/Control Relay Output Points

Available in

Sl No

DNP3 Point

Description

VTI

VTII

May be mapped multiple times for any given phase. This is a placeholder for customer mapping purposes. It will always return '0'

Dummy

Yes

Yes

1

2

Trip Contacts

Trip Recloser Contacts

Yes

Yes

3

Contacts Close

Close Recloser Contacts

Yes

Yes

Trip Recloser Contacts and drop the Manual Handle (yellow). NOTE: Once SCADA Master issues this command there is no way of closing back the contacts remotely from SCADA Master

4

Lockout

Yes

5

Non-Reclose On

Enable Non-Reclose Mode

Yes

Yes

6

Non-Reclose Off

Disable Non-Reclose Mode

Yes

Yes

7

HLT On

Turn on HLT Function

Yes

Yes

8

HLT Off

Turn off HLT Function

Yes

Yes

9

Beacon Flash On

Flash Beacon for 1 minute

Yes

Yes

10

Beacon Flash Off

Turn off beacon flashing

Yes

Connect to Recloser

11

Establish connection with Recloser

Yes

Yes

Disconnect from Recloser

12

Disconnect from Recloser

Yes

Yes

Clear all temporary operation event counters ("This Count"), including 1-4th shot counters for the VTII.

Clear Resettable Operation Counters

13

Yes

Yes