Versa-Tech® Terminal Unit (10F)
4. Counters
Available in
Sl No DNP3 Point
Description
VTI
VTII
May be mapped multiple times for any given phase. This is a placeholder for customer mapping purposes. It will always return '0' Total Overcurrent Operations is the total number of "OVERCURRENT" Operations seen in the recloser life after production. This counts anytime the bottle opens on a fault (NR, HLT, Min Trip, Cold Load) Total Operations, including Sequence Coordination events, seen in the recloser life after production. Total Mechanical Operations (anything that has opened the bottle, including manual opening). Temporary Operation event counter counts overcurrent and sequence coordination events from its last reset.
1
Dummy
Yes
Yes
Total Overcurrent Operations
2
•
Yes
3
Total Operations
Yes
Yes
Total Mechanical Operations
4
•
Yes
Resettable Operation event counter Resettable 1st shot event counter Resettable 2nd shot event counter Resettable 3rd shot event counter Resettable 4th shot event counter
5
Yes
Yes
6
Number of first shots occurred
•
Yes
7
Number of second shots occurred
•
Yes
8
Number of third shots occurred
•
Yes
9
Number of fourth shots occurred
•
Yes
Page 10F-7 | February 2014