Turner Substation Catalog (CA10103E )
TECO-RUPTER TYPES Type RLS TECO-Rupters can break load up to 2000A and interrupt line charging up to 100A from 15kV through 34kV; and can interrupt up to 2000A in parallel circuits from 15kV through 230kV. Type RLM TECO-Rupters can break load up to 3000A and interrupt line charging up to 100A from 15kV through 34kV; and can interrupt up to 3000A in parallel circuits from 15kV through 230kV. Type RLB TECO-Rupters can break load up to 2000A, interrupt line charging up to 100A, and can interrupt up to 2000A in parallel circuits from 15kV through 230kV.
TECO-Rupter Ratings and Types
Type RLS Loop Breaking*
Type RLM Loop Breaking*
Type RLB Loop Breaking*
Maximum kV
Loop Splitting
Line Charging
Loop Splitting
Line Charging
Loop Splitting
Line Charging
15
2000A 2000A
100A
3000A 3000A
100A
2000A 2000A
100A
23
2000A 2000A
100A
3000A 3000A
100A
2000A 2000A
100A
34
2000A 2000A
100A
3000A 3000A
100A
2000A 2000A
100A
46
2000A
3000A
2000A 2000A
100A
69
2000A
3000A
2000A 2000A
100A
115
2000A
3000A
2000A 2000A
100A
138
2000A
3000A
2000A 2000A
100A
151
2000A
3000A
2000A 2000A
100A
230
2000A
3000A
2000A 2000A
100A
* Load Break Capacity at 70% Power Factor. For capacitor bank applications, contact the factory. NOTE: In General, type RLS TECO-Rupters are used in loop split circuits up to 2000A, type RLM TECO-Rupters are used in loop split circuits up to 3000A, and type RLB TECO-Rupters are used in full load break applications up to 2000A.