Transmission Products (T-1201)
Suspension Insulators
ANSI Values
IEC Values
Section Length High Leak Design
Critical Impulse Negative (kV)
60-Hz 1-Minute Wet Withstand (kV)
Impulse Positive Withstand (kV)
Impulse Negative Withstand (kV)
350 355 395 400 510 520 625 625 725 735 800 805 860 875 935 945
145 150 165 170 210 215 260 265 300 310 330 335 360 365 385 390 410 420 435 445 465 470 490 495 515 520 540 545 565 570 585 590 610 615 630 635 655 660 675 680 700 705 720 720 740 745 760 765 780 780 795 800 815 820 835 840
315 330 350 360 445 455 540 550 630 640 690 705 755 765 810 825 870 885 930 945
300 315 330 345 430 445 530 540 625 635 690 700 750 765 810 825 875 890 940 950
Section Length Standard Design
QUADRI*SIL ®
1005 1015 1075 1080 1140 1150 1210 1220 1275 1285 1345 1350 1420 1425 1485 1500 1545 1565 1605 1615 1670 1675 1725 1735 1790 1800 1855 1860 1915 1925 1980 1985 2040 2050 2100 2110 2160 2170 2220 2230
Section Length Adjustment Table
Base End Fittings: Y-clevis-Ball (201)
990 1000 1050 1060 1110 1120 1165 1175 1220 1235 1280 1290 1340 1350 1395 1405 1445 1460 1505 1515 1560 1570 1615 1620 1665 1680 1720 1730 1775 1785 1830 1840 1880 1890 1935 1940
1000 1010 1060 1075 1125 1130 1180 1195 1240 1255 1305 1310 1360 1370 1420 1430 1475 1485 1530 1545 1590 1600 1650 1660 1705 1715 1760 1770 1815 1825 1870 1885 1925 1935 1980 1990
Top and BottomEnd Fitting Digits (“e”&“f”) in CatalogNumber
Length Change Inches (mm)
Top Fitting Bottom Fitting
Y-Clevis Eye
Eye ANSI 52-11 Ball
200 001 000 301 A07 800 807
1.71 (43) 0.31 (8) 2.02 (51)
Eye
Eye
ANSI 52-11 Socket IEC 20 mm Socket
ANSI 52-11 Ball IEC 20 mm Ball Eye IEC 20 mm Ball
-0.71 (-18) 0.26 (7)
Clevis IEC 19-L Clevis IEC 19-L
0.80 (20) 0.06 (2)
NOTE: To determine the section length for an insulator with a different end fitting combination, please add or subtract the displayed length change in the table above. For configurations not shown, use the Catalog Number Key or contact your HPS representative. Dimensional and electrical values displayed in main table are for an insulator with Y-clevis and Ball end fittings. For voltages above 400 kV, other section lengths, or end fitting combinations, please contact your HPS representative. Electrical values are without corona ring. For voltages equal to or greater than 220 kV, refer to page 218 for corona rings and associated physical/electrical changes to the above data. Dimensions are within allowable tolerances as specified by IEC 61109 and ANSI C29.12.
Page 247 | July 2016