Transmission Products (T-1201)

Tee Connectors Tee-Taps Compression Cable to Pad — Open Run ACSS/TWConductors

ALUMINUM ORT21STW

Tee taps listed below are rated for use on ACSS/ TW conductors when installed with Fargo ® type HTJC, high-temperature joint compound. Tap pad holes have NEMA spacing.

Length Before Compression

Material: Body – aluminum alloy Pad – cast aluminum

1.75 [44]

Min Flat

1.75 [44]

Min Flat

B

IDENTIFICATION:

.56 [14] Dia Holes

Conductor Type & Diameter Range Die Size, Minimum Press Size Part Number, Date Code

1.75 [44]

Pad Width

Pad Width

Product Data and Conductor Size

JUMPER TERMINALS

ACSS/TW Conductor Range

Pad Details

Min Press Size Tons

Fargo Catalog Number

Length Before Compression Inches (mm)

Net Weight lb (kg)

Die Size (1)

Outside Diameter Inches (mm) 0.547-0.611 (13.9 - 15.5) 0.630-0.695 (16.0 - 17.7) 0.702-0.776 (17.8 - 19.7) 0.789-0.858 (20.0 - 21.8)

Bolt Holes

Width Inches (mm)

Kcmil Size (Type)

ORT2107STW ORT2107CSTW ORT2108STW ORT2108CSTW ORT2109STW ORT2109CSTW ORT2110STW ORT2110CSTW

2 4 2 4 2 4 2 4

2.0 (51) 3.0 (76) 2.0 (51) 3.0 (76) 2.0 (51) 3.0 (76) 2.0 (51) 3.0 (76)

12.7 (323) 13.7 (348) 13.5 (343) 14.5 (368) 15.6 (398) 16.6 (422) 16.3 (414) 17.3 (439)

0.90 (0.41) 0.97 (0.44) 1.1 (0.50) 1.2 (0.60) 1.5 (0.68) 1.6 (0.73) 1.9 (0.86) 2.0 (0.91)

266.8 (T16)

07CD

12

08CD 76AH

336.4 (T16 & T23)

12

397.5 (T13 & T16), 477 (T13)

09CD

12

477 (T16 & T23), 556.5 (T13 & T16), 565.3 (T16), 571.7 (T13)

10CD 24AH

60

ORT2111STW 0.880-0.930 (22.4 - 23.6)

636 (T13 & T16)

18.1 (459)

11CD

60

4

3.0 (76)

2.6 (1.18)

ORT2112STW ORT2112DSTW

0.960-1.010 (24.4 - 25.7)

762.8 (T13 & T16), 795 (T7, T13 & T16)

3.0 (76) 4.0 (102)

19.5 (495) 20.5 (521)

3.3 (1.50) 3.5 (1.59)

12CD

60

4

13CD 30AH

795 (T23)

ORT2113STW ORT2113DSTW

1.046-1.108 (26.6 - 28.1)

3.0 (76) 4.0 (102)

21.3 (541) 22.3 (566)

3.9 (1.77) 4.1 (1.86)

4

60

795 (T23), 900 (T13), 954 (T7 & T13), 959.6 (T16), 966.2 (T13), 1033.5 (T7) 1033.5 (T13), 1113 (T7 & T13), 1158 (T7), 1158.4 (T13), 1192.5 (T7)

13CD

ORT2114STW ORT2114DSTW

1.125-1.196 (28.6 - 30.4)

3.0 (76) 4.0 (102)

22.2 (564) 23.3 (589)

14CD 34AH

5.1 (2.31) 5.3 (2.40)

4

60

1192.5 (T13), 1233.3 (T13), 1272 (T7 & T13), 1351.5 (T7 & T13), 1431 (T7)

ORT2115STW ORT2115DSTW

1.212-1.300 (30.8 - 33.0)

3.0 (76) 4.0 (102)

24.0 (610) 25.0 (635)

15CD 36AH

5.9 (2.67) 6.1 (2.77)

4

60

ORT2116STW ORT2116DSTW

1.290-1.382 (32.8 - 35.1)

1431 (T7 & T13), 1433.6 (T13) 1533.3 (T13), 1590 (T7) 1590 (T13), 1657.4 (T7), 1780 (T8) 1926.9 (T13), 1949.6 (T7)

3.0 (76) 4.0 (102)

25.0 (635) 26.0 (660)

16CD 38AH 17CD 19CD 44AH 19CD

8.1 (3.67) 8.3 (3.76)

4

60

ORT2117STW 1.385-1.455 (35.2 - 37.0)

4.0 (102)

26.0 (660)

60

8.5 (3.88)

4

ORT2119STW 1.504-1.608 (38.2 - 40.8)

4

4.0 (102)

28.8 (732)

100

11.3 (5.13)

2156 (T8)

NOTE: Install with Fargo type HTJC inhibitor compound. Tees are suitable for EHV applications on conductors over 1.0 in (25.4 mm) O.D. (1) Hex dies not available for some sleeve and conductor combinations. If no AH die listed for conductor, use only the CD die shown.

Page 134 | July 2016

Made with FlippingBook - Online magazine maker