Transmission Connectors - Assemblies (TH)
Jumper Support, 2-Bundle Conductor Single Insulator with Weights 30k lb Assembly, 138kV - 230kV
ASSEMBLY TAJ21
0.88
Ø.63
1
2.78
Section Length
2
Inclusion of Ring Based on Voltage
3
2.75
4
Conductor Range: 0.974"-1.259"
5
3.63
18.00
Base Assembly Bill of Material
Item Part Number
Description
Quantity
Material
UBS lb
1
AS25LBNK
Anchor Shackle
1
Forged Steel
30,000
2
See Chart
Insulator, ANSI 52-5
1
Polymer
—
3
SYC30
Socket Y-Clevis
1
Ductile Iron
30,000
YPJ21018215200 See Note 1
4
Jumper Yoke w/Weights
1
Aluminum
10,000
5
See Note 2
Armor Rods
1
Aluminum
—
H 24
Typical Insulator Selection
Line Voltage (kV)
Quadri*Sil® Part Number
Section Length Inches
SML lb
Corona Ring
138
S030043S2010
54.9
30,000
—
161
S030056S2010
67.8
30,000
—
230
S030073S201A
85.1
30,000
8”Line End
NOTE: For quoting/ordering instructions, see Assemblies section. (1) For jumper yokes with other conductor ranges or different amounts of weight, please contact HPS. (2) See Armor Rod section for rod set based on conductor application.