Transmission And Substation Foundations - Technical Design Manual
APPENDIX B: LOAD TESTS
Static Axial Load Tests (Compression/Tension)
7 ft (2M) minimum Between Test Pile and Reaction Anchor
Dial Indicator Hydraulic Jack/Cylinder
Reference Beams
Load Beams
Spreader Beam
Cribbing
Reaction Anchor (4 minimum)
Basic Compression Field Test Set-up Figure B-1
Pre-Production Test Schedule, Table B-1 Cyclical Load Increments (%Dl/100) Load Increment
Hold Period (Min.)
Load Increment
Hold Period (Min.)
AL
1
AL
1
0.20DL
4
0.50DL
4
0.40DL
4
1.00DL
4
0.60DL
4
1.20DL
4
0.80DL
4
1.40DL
4
1.00DL
4
1.60DL
4
0.75DL
4
1.80DL
4
0.50DL
4
2.00DL
10
0.25DL
4
1.50DL
4
1.00DL
4
0.50DL
4
AL
5
AL = Alignment Load, usually 10% of DL; DL = Design (Working) Load
www.hubbell.com/hubbellpowersystems | B-3
Made with FlippingBook - Online catalogs