Transmission And Substation Foundations - Technical Design Manual (TD06088E)
Nominal, LRFD Design, and ASD Allowable Compression Strengths of Drivecast Piles, Type RS3500.300 Central Shafts in Soft Soil 1,2,3
Nominal, LRFD Design, and ASD Allowable Compression Strengths kip (kN) Soft Soil Pinned Fixed
Grout Column Diameter
Nominal
Design
Allowable
Nominal
Design
Allowable
No Grout
90.66 (403.3) 104.27 (463.8) 227.20 (1010.6) 273.01 (1214.4) 326.90 (1454.1) 388.90 (1729.9) 458.90 (2041.3) 536.72 (2387.4) 622.20 (2767.7)
81.59 (362.9) 78.20 (347.9) 170.40 (758.0) 207.76 (924.2) 245.18 (1090.6) 291.68 (1297.5) 344.17 (1530.9) 402.54 (1790.6) 466.65 (2075.8)
54.28 (241.4) 52.14 (231.9) 113.60 (505.3) 136.50 (607.2) 163.45 (727.1) 194.45 (865.0) 229.45 (1020.6) 268.36 (1193.7) 311.10 (1383.8)
110.01 (489.3) 131.39 (584.5) 275.51 (1225.5) 326.56 (1452.6) 385.18 (1713.4) 451.33 (2007.6) 524.92 (2335.0) 605.82 (2694.8) 693.90 (3086.6)
99.01 (440.4) 98.55 (438.4) 206.63 (919.1) 244.92 (1089.5) 288.88 (1285.0) 338.50 (1505.7) 393.69 (1751.2) 454.36 (2021.1) 520.43 (2315.0)
65.88 (293.0) 65.70 (292.2) 137.75 (612.7) 163.28 (726.3) 192.59 (856.7) 225.67 (1003.8) 262.46 (1167.5) 302.91 (1347.4) 346.95 (1543.3)
Grout Inside
8” OD 9” OD 10” OD 11” OD 12” OD 13” OD 14” OD
Nominal, LRFD Design, and ASD Allowable Compression Strengths of Drivecast Piles, Type RS4500.337 Central Shafts in Soft Soil 1,2,3
Nominal, LRFD Design, and ASD Allowable Compression Strengths kip (kN) Soft Soil Pinned Fixed
DRAWINGS AND RATINGS
Grout Column Diameter
Nominal
Design
Allowable
Nominal
Design
Allowable
No Grout
156.30 (700.5) 190.46 (853.6) 302.24 (1354.7) 347.89 (1559.3) 440.88 (1976.1) 461.50 (2068.5) 529.87 (2374.9)
140.67 (630.5) 142.84 (640.2) 226.68 (1016.0) 260.92 (1169.4) 300.66 (1347.6) 346.12 (1551.3) 397.41 (1781.2)
93.59 (419.4) 95.23 (426.8) 151.12 (677.3) 173.94 (779.6) 200.44 (898.4) 230.75 (1034.2) 264.94 (1187.5) 303.02 (1347.9)
175.30 (785.7) 219.25 (982.7) 344.32 (1543.3) 395.11 (1770.9) 453.02 (2030.5) 518.18 (2322.5) 590.67 (2647.5)
157.77 (707.1) 164.44 (737.0) 258.24 (1157.4) 296.33 (1328.2) 339.76 (1522.8) 388.64 (1741.9) 443.00 (1985.6)
104.97 (470.4) 109.63 (491.3) 172.16 (771.6) 197.56 (885.5) 226.51 (1015.2) 259.09 (1161.2) 295.33 (1323.7)
Grout Inside
8” OD 9” OD 10” OD 11” OD 12” OD 13” OD 14” OD 15” OD 16” OD
606.03 (2965.76) 454.53 (2021.85)
670.46 (2982.36) 502.85 (2236.79) 335.23 (1491.18)
689.92 (3068.92) 517.44 (2301.69) 344.96 (1534.46) 757.52 (3369.62) 568.14 (2527.21) 378.76 (1684.81) 781.42 (3475.93) 586.06 (2606.93) 390.71 (1737.97) 851.77 (3788.86) 638.83 (2841.66) 425.88 (1894.41) 880.42 (3916.30) 660.32 (2947.25) 440.21 (1958.15) 953.14 (4239.78) 714.85 (3179.81) 476.57 (2119.89)
Nominal, LRFD Design, and ASD Allowable Compression Strengths of Drivecast Piles, Type RS8625.250 Central Shafts in Soft Soil 1,2,3
Nominal, LRFD Design, and ASD Allowable Compression Strengths kip (kN) Soft Soil Pinned Fixed
Grout Column Diameter
Nominal 272.91 490.33 674.76 749.04 830.02 917.93 1012.92 1115.13 1224.62 1341.44 1465.58 1597.04 1735.76
Design 245.62 367.75 506.07 561.78 622.52 688.45 759.69 836.34 918.46 1006.08 1099.19 1197.78 1301.82
Allowable
Nominal 280.85 513.39 708.49 787.13 872.47 964.63 1063.69 1169.72 1282.76 1402.82 1529.92 1664.02 1805.12
Design 252.76 385.04 531.37 590.35 654.35 723.47 797.76 877.29 962.07 1052.12 1147.44 1248.02 1353.84
Allowable
No Grout
163.42 245.17 337.38 374.52 415.01 458.97 506.46 557.56 612.31 670.72 732.79 798.52 867.88
168.17 256.69 354.24 393.56 436.23 482.31 531.84 584.86 641.38 701.41 764.96 832.01 902.56
Grout Inside
12” OD 13” OD 14” OD 15” OD 16” OD 17” OD 18” OD 19” OD 20” OD 21” OD 22” OD
For SI: 1 kip = 4.448 kN. 1 Refer to Section 4.1.3 of ESR-2794 for descriptions of fixed condition, pinned condition, soft soil.
2 Strength ratings are based on a design corrosion level of 50-years and presume the supported structure is braced in accordance with IBC Section 1808.2.5, and the lead section with which the extension is used will provide sufficient helix capacity to develop the full shaft capacity. 3 Column length to “fixity” of shaft in soil = 10 feet (3 meters)