Transmission And Substation Foundations - Technical Design Manual (TD06088E)
Nominal, LRFD Design, and ASD Allowable Compression Strengths of CHANCE ® Type SS225 Grouted Shaft Piles in Soft Soil 1,2,3
Nominal, LRFD Design, and ASD Allowable Compression Strengths kip (kN) Soft Soil Pinned Fixed
Grout Column Diameter
Nominal 70.9 (315) 154.9 (689) 228.8 (1018) 354.3 (1576) 466.1 (2073)
Design
Allowable 42.5 (189) 77.5 (345) 114.4 (509) 177.1 (788) 233.1 (1037)
Nominal
Design
Allowable 83.2 (370) 140.9 (627) 181.6 (808) 241.1 (1072) 295.7 (1315)
No Grout
63.8 (284) 116.2 (517) 171.6 (763) 265.7 (1182) 349.6 (1555)
139.0 (618) 281.8 (1254) 363.2 (1171) 482.3 (2145) 591.3 (2630)
125.1 (556) 211.4 (940) 272.4 (1212) 361.7 (1609) 443.5 (1973)
6” OD 7” OD
8.5” OD 10” OD
Nominal, LRFD Design, and ASD Allowable Compression Strengths of CHANCE ® Type RS2875.203 Grouted Shaft Piles in Soft Soil 1,2,3
Nominal, LRFD Design, and ASD Allowable Compression Strengths kip (kN) Soft Soil Pinned Fixed
Grout Column Diameter
Nominal 42.0 (187) 95.7 (426) 160.1 (712)
Design
Allowable 25.1 (112) 47.8 (213) 80.1 (356)
Nominal 55.5 (247) 125.7 (559) 203.2 (904)
Design
Allowable 33.2 (148) 62.8 (279) 101.6 (452)
No Grout
37.8 (168) 71.8 (319) 120.1 (534)
49.9 (222) 94.3 (419) 152.4 (678)
6” OD 8” OD
Nominal, LRFD Design, and ASD Allowable Compression Strengths of CHANCE ® Type RS2875.276 Grouted Shaft Piles in Soft Soil 1,2,3
Nominal, LRFD Design, and ASD Allowable Compression Strengths kip (kN) Soft Soil Pinned Fixed
Grout Column Diameter
Nominal 55.2 (246) 114.3 (508) 181.4 (807)
Design
Allowable 33.0 (147) 57.1 (254) 90.7 (403)
Nominal 73.9 (329) 147.7 (657) 226.9 (1009)
Design
Allowable 44.3 (197) 73.9 (329) 113.5 (505)
No Grout
49.7 (221) 85.7 (381) 136.0 (605)
66.5 (296) 110.8 (493) 170.2 (757)
6” OD 8” OD
Nominal, LRFD Design, and ASD Allowable Compression Strengths of CHANCE ® Type RS3500.300 Grouted Shaft Piles in Soft Soil 1,2,3
Nominal, LRFD Design, and ASD Allowable Compression Strengths kip (kN) Soft Soil Pinned Fixed
DRAWINGS AND RATINGS Grout Column Diameter
Nominal 90.7 (403) 145.1 (645) 179.3 (798) 216.7 (964) 314.4 (1399)
Design
Allowable 54.3 (242) 72.5 (322) 89.6 (399) 108.4 (482) 157.2 (699)
Nominal 110.0 (49) 175.6 (781) 214.1 (952) 257.3 (1145) 365.6 (1626)
Design
Allowable 65.9 (293) 87.8 (391) 107.0 (476) 128.6 (572) 182.8 (813)
No Grout
81.6 (363) 108.8 (484) 134.4 (598) 162.5 (723) 235.8 (1049)
99.0 (440) 131.7 (586) 160.6 (714) 193.0 (859) 274.2 (1220)
6” OD 7” OD 8” OD 10” OD
Nominal, LRFD Design, and ASD Allowable Compression Strengths of CHANCE ® Type RS4500.337 Grouted Shaft Piles in Soft Soil 1,2,3
Nominal, LRFD Design, and ASD Allowable Compression Strengths kip (kN) Soft Soil Pinned Fixed
Grout Column Diameter
Nominal
Design
Allowable 93.6 (416) 97.6 (434) 115.2 (512) 137.1 (610) 186.4 (829)
Nominal
Design
Allowable 105.0 (467) 110.3 (491) 129.8 (577) 153.2 (681) 207.5 (923)
No Grout
156.3 (695) 195.3 (869) 230.4 (1025) 274.2 (1220) 372.8 (1658)
140.7 (626) 146.5 (652) 172.8 (769) 205.6 (915) 279.6 (1244)
175.3 (780) 220.6 (981) 259.6 (1155) 306.4 (1363) 415.0 (1846)
157.8 (702) 165.5 (736) 194.7 (866) 229.8 (1022) 311.3 (1385)
6” OD 7” OD 8” OD 10” OD
For SI: 1 kip = 4.448 kN. 1 Refer to Section 4.1.3 of ESR-2794 for descriptions of fixed condition, pinned condition, soft soil.
2 Strength ratings are based on a design corrosion level of 50-years and presume the supported structure is braced in accordance with IBC Section 1808.2.5, and the lead section with which the extension is used will provide sufficient helix capacity to develop the full shaft capacity. 3 Column length to “fixity” of shaft in soil = 10 feet (3 meters)
Page 6-62 | Hubbell Power Systems, Inc. | All Rights Reserved | Copyright © 2019
Made with FlippingBook - Online catalogs