Transmission And Substation Foundations - Technical Design Manual (TD06088E)

SS225 HELICAL PILE AND ANCHOR PRODUCT SPECIFICATIONS

Hot Rolled Round-Cornered-Square (RCS) Solid Steel Bars per ASTM A29; modified AISI 1530 with 90 ksi minimum yield strength

SHAFT

Corroded 2.237 in 56.8 mm

Shaft Size

2.25 in 57 mm

Corroded

2.04 in 4

84.9 cm 4

Moment of Inertia (I)

1.99 in 4

82.83 cm 4

Corroded

5.0 in 2

32.1 cm 2

Shaft Area (A)

4.93 in 2

31.81 cm 2

Corroded

1.81 in 3

29.7 cm 3

Section Modulus (S x-x )

1.79 in 3

29.37 cm 3

Corroded 8.43 in 21.41 cm

Perimeter

8.5 in 21.5 cm

Coupling

Integral Forged Square Deep Socket

One 1-1/4 inch Diameter ASTM A193 Grade B7 Hex Head Bolt with Threads Excluded from Shear Planes 0.5 inch Thick, Formed on Matching Metal Dies, ASTM A656 or A1018 Grade 80 Hot Dip Galvanized per ASTM A153 Class B-1, 3.1 mil minimum thickness or Bare Steel

Coupling Bolts

DRAWINGS AND RATINGS

Helix Plates

Coatings

TORQUE PROPERTIES Torque Correlation Factor

10 ft -1

33 m -1

Torque Rating

21,000 ft-lb

28,475 N-m

STRUCTURAL CAPACITY

Nominal LRFD Design 200 kip 890 kN 150 kip 667 kN

Tension Strength

Allowable Tension Strength

100 kip

445 kN

Assembly of SS225 Figure 6-14

TORQUE CORRELATED CAPACITY Capacity Limit Based

Ultimate Allowable 210 kip 934 kN 105 kip 467 kN

on Torque Correlation, Tension / Compression

ASD Allowable Compression Strengths of CHANCE ® Type SS225 Helical Pile Lead & Extension Sections 1,2

ASD Allowable Axial Compression Strength kip (kN) Firm Soil

Section Type & Helix Count

Soft Soil

Fixed

Pinned

Fixed

Pinned

See Helix Strength Table Above, except single 6 & 8 inch - 83.2 (370.1)

Lead, Single Helix

See Helix Strength Table Above See Helix Strength Table Above

42.5 (189)

Lead, 2-Helix 8”-10” Lead, 2-Helix 10”-12” Lead, 2-Helix 12”-14” Lead, 2-Helix 14”-14”

169.9 (755.8) 146.5 (651.6) 133.8 (595.1) 126.4 (562.2) 198.6 (883.4) 198.6 (883.4)

149.8 (666.3) 146.5 (650.7) 133.8 (595.1) 126.4 (562.3) 149.8 (666.3) 149.8 (666.3)

83.2 (370.1)

42.5 (189)

Lead, Multi-Helix

83.2 (370.1) 83.2 (370.1)

42.5 (189) 42.5 (189)

Extension

For SI: 1 kip = 4.448 kN. 1 Refer to Section 4.1.3 of ESR-2794 for descriptions of fixed condition, pinned condition, soft soil and firm soil.

2 Strength ratings are based on a design corrosion level of 50-years and presume the supported structure is braced in accordance with IBC Section 1808.2.5, and the lead section with which the extension is used will provide sufficient helix capacity to develop the full shaft capacity.

Page 6-25 | Hubbell Power Systems, Inc. | All Rights Reserved | Copyright © 2019

Made with FlippingBook - Online catalogs