SS225 HELICAL PILE AND ANCHOR PRODUCT SPECIFICATIONS
Hot Rolled Round-Cornered-Square (RCS) Solid Steel Bars per ASTM A29; modified AISI 1530 with 90 ksi minimum yield strength
SHAFT
Corroded 2.237 in 56.8 mm
Shaft Size
2.25 in 57 mm
Corroded
2.04 in 4
84.9 cm 4
Moment of Inertia (I)
1.99 in 4
82.83 cm 4
Corroded
5.0 in 2
32.1 cm 2
Shaft Area (A)
4.93 in 2
31.81 cm 2
Corroded
1.81 in 3
29.7 cm 3
Section Modulus (S x-x )
1.79 in 3
29.37 cm 3
Corroded 8.43 in 21.41 cm
Perimeter
8.5 in 21.5 cm
Coupling
Integral Forged Square Deep Socket
One 1-1/4 inch Diameter ASTM A193 Grade B7 Hex Head Bolt with Threads Excluded from Shear Planes 0.5 inch Thick, Formed on Matching Metal Dies, ASTM A656 or A1018 Grade 80 Hot Dip Galvanized per ASTM A153 Class B-1, 3.1 mil minimum thickness or Bare Steel
Coupling Bolts
DRAWINGS AND RATINGS
Helix Plates
Coatings
TORQUE PROPERTIES Torque Correlation Factor
10 ft -1
33 m -1
Torque Rating
21,000 ft-lb
28,475 N-m
STRUCTURAL CAPACITY
Nominal LRFD Design 200 kip 890 kN 150 kip 667 kN
Tension Strength
Allowable Tension Strength
100 kip
445 kN
Assembly of SS225 Figure 6-14
TORQUE CORRELATED CAPACITY Capacity Limit Based
Ultimate Allowable 210 kip 934 kN 105 kip 467 kN
on Torque Correlation, Tension / Compression
ASD Allowable Compression Strengths of CHANCE ® Type SS225 Helical Pile Lead & Extension Sections 1,2
ASD Allowable Axial Compression Strength kip (kN) Firm Soil
Section Type & Helix Count
Soft Soil
Fixed
Pinned
Fixed
Pinned
See Helix Strength Table Above, except single 6 & 8 inch - 83.2 (370.1)
Lead, Single Helix
See Helix Strength Table Above See Helix Strength Table Above
42.5 (189)
Lead, 2-Helix 8”-10” Lead, 2-Helix 10”-12” Lead, 2-Helix 12”-14” Lead, 2-Helix 14”-14”
169.9 (755.8) 146.5 (651.6) 133.8 (595.1) 126.4 (562.2) 198.6 (883.4) 198.6 (883.4)
149.8 (666.3) 146.5 (650.7) 133.8 (595.1) 126.4 (562.3) 149.8 (666.3) 149.8 (666.3)
83.2 (370.1)
42.5 (189)
Lead, Multi-Helix
83.2 (370.1) 83.2 (370.1)
42.5 (189) 42.5 (189)
Extension
For SI: 1 kip = 4.448 kN. 1 Refer to Section 4.1.3 of ESR-2794 for descriptions of fixed condition, pinned condition, soft soil and firm soil.
2 Strength ratings are based on a design corrosion level of 50-years and presume the supported structure is braced in accordance with IBC Section 1808.2.5, and the lead section with which the extension is used will provide sufficient helix capacity to develop the full shaft capacity.
Page 6-25 | Hubbell Power Systems, Inc. | All Rights Reserved | Copyright © 2019