Three-Phase Programmable Resettable Sectionalizer (3Ø PRS) (10DDDD)
Three-Phase Programmable Resettable Sectionalizer
Technical Specifications
Rated Power Frequency
60 Hz/50 Hz
Rated Voltage (BIL)
15kV (110kV BIL) 27kV (125kV BIL) 38kV (150/170kV BIL)
Rated Continuous Current
300 Amps
Minimum Line Current
10 Amps
Minimum Actuating Current
Programmable between 16 A and 480 A
Number of Counts:
Programmable for 1, 2, 3 or 4 counts
Reset time:
Programmable, 30 seconds to 300 seconds with resolution of 1 second
Inrush detection time
Less than 1 cycle
Types of inrush currents detected: Symmetrical and Asymmetrical Method of inrush currents detection: Fourier Analysis (FFT) Deadline detection: ≤ 500mA Total execution time: 130 msec (± 20 msec) Short time current withstand, 15 cycle (at 60 Hz):
8600 Amps Sym. 4000 Amps Sym. 3200 Amps Sym.
1 second: 3 seconds:
Momentary current rating:
12,000 Amps. Asym.
*Current measurement accuracy:
±5%
Temperature range:
-40°C to +60°C
Maximum Thermal Rating:
300 A continuous current
Surge current withstand
65kA, per ANSI C37.63
Electromagnetic interference
per ANSI C37.90.2
USB port
Rated IP68
Note: Ratings are based on testing conducted at 60Hz
* With 5% accuracy, if the unit is programmed for 50 A actuating current, then the unit will pick-up the count at 52.5 A and above but ignore a count at 47.5 A and below.
For Catalog Number System, see following pages.