Substation Connectors (Combined)
TYPE BCL COPPER COMPRESSION CONNECTOR (CONTINUED)
Product Data & Conductor Size
COPPER CONDUCTOR RANGE
DIMENSIONS INCHES (MM)
APPROX. WT. EACH LBS. (KG)
CATALOG NUMBER
FIG. NO.
DIE REF.
SA 34
CABLE
DIA.
L
A
B
K
T
W
8.63 (219.20) 9 (228.6) 9.75 (247.65) 8.88 (225.55) 9 (228.6) 9.75 (247.65) 10.18 (258.57) 11.25 (285.75) 11.18 (283.97) 12.38 (314.45)
4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6) 5 (127.0) 5 (127.0) 6 (152.4) 6 (152.4)
3-1/4 (82.55) 3-1/4 (82.55) 4-1/4 (107.95) 3-1/4 (82.55) 3-1/4 (82.55) 4-1/4 (107.95) 3-1/4 (82.55) 4-1/4 (107.95) 3-1/4 (82.55) 4-1/4 (107.95)
5/8 (15.88) 5/8 (15.88) 1-1/8 (25.58) 5/8 (15.88) 5/8 (15.88) 1-1/8 (25.58) 5/8 (15.88) 1-1/8 (25.58) 5/8 (15.88) 1-1/8 (25.58)
1/2 (12.7) 5/16 (7.9) 1/2 (12.7)
2 (50.8) 3 (76.2) 4 (101.6) 2 (50.8) 3 (76.2) 4 (101.6) 3 (76.2) 4 (101.6) 3 (76.2) 4 (101.6)
2.0 (.9)
BCL075B2 1
2.2 (1.0) 4.2 (1.9) 3.1 (1.4) 3.3 (1.5) 4.2 (1.9) 7.5 (3.4) 9 (4.1) 11 (5.0) 13 (5.9)
.998 (25.35)
BCL075C 2
750 MCM
1.312
BCL075D 2
5/8 (15.88)
BCL100B2 1
1.152 (29.26)
3/8 (9.5) 1/2 (12.7)
BCL100C 2
1000 MCM
1.500
BCL100D 2
5/8 (15.88) 5/8 (15.88) 3/4 (19.05) 3/4 (19.05)
BCL150C 2
1.412 (35.86)
1500 MCM
2.125
BCL150D 2
BCL200C 2
1.632 (41.45)
2000 MCM
2.375
BCL200D 2
CONVENTIONAL COMPRESSION DIE INFORMATION
DIE INDEX
KEARNEY
ALCOA
BURNDY
T&B
.640
5/8
73AH
243
52
.840
.840 OR .849
74AH
249
76
1.000
1.000
75AH
251
1.125
1-1/8
76AH
490, 347, 316
96
1.312
1-5/16
20AH
327, 317, 426, 300
106
1.500
1-1/2
24AH
318, 261, 608
125
1.843
K6030AH
30AH
292, 302, 352, 579
150
2.125
2-1/8
34AH
422, 575
160, 161
2.375
2-3/8
38AH
478, 728
189
2.937
2-15/16
48AH
250
NOTES: 1. Crimps should overlap and start from the inside working outward with the last crimp extending past the end of the connector. 2. It is recommended that a light coat of lubricant (such as Anderson’s I55 grease) be applied to the crimping face of the dies.
ANDERSON ™
HUBBELL ® POWER SYSTEMS
FARGO ®
October 2016
Made with FlippingBook flipbook maker