Substation Connectors (Combined)
Tungsten - Arc
TUNGSTEN DIA. INCHES
WALL THICK NESS
GAS CUP DIA. INCHES
ARGON FLOW
4043 FILLER ROD SIZE
IPS SIZE
AMPERES
CFH PREHEAT °F NO. PASSES
1/2
.108
125-150
3/8
1/8
20
None
1
1/8
3/4
.113
125-150
3/8
1/8
20
None
1
1/8
1
.133
125-150
3/8
1/8
30
None
1
1/8
1-1/4
.140
160-170
3/8
1/8
30
None
1
1/8
1-1/2
.144
160-170
3/8
1/8
30
None
1
1/8
2
.154
170-190
1/8
1/8
30
None
1
3/16
2-1/2
.203
170-190
1/2
3/16
40
None
1
3/16
Optional to 400° F Optional to 400° F Optional to 400° F Optional to 400° F Optional to 400° F Optional to 400° F
3
.216
170-190
1/2
3/16
40
1
3/16
3-1/2
.226
170-190
1/2
3/16
40
1
3/16
4
.237
180-200
1/2
3/16
50
1
3/16
4-1/2
.247
180-200
1/2
3/16
50
1
3/16
5
.258
180-200
1/2
3/16
50
1 or 2
3/16
6
.280
180-200
1/2
3/16
50
1 or 2
3/16
Flat Bar
4043 FILLER ROD SIZE
FLAT BAR THICKNESS AMPERES
GAS CUP DIA. INCHES
TUNGSTEN DIA.
ARGON FLOW CFH
NO. PASSES
PREHEAT °F
1/8
125
3/8
1/8
30
None
1
1/8
1/4
150
1/2
3/16
30
None
1
3/16
3/8
300
1/2
3/16
50
Optional to 400° F
1
1/4
1/2
400
5/8
1/4
50
400° F
1 or 2
1/4
3/4
450
5/8
1/4
50
400° F
2
5/16
1
500
5/8
5/16
50
400° F
2
5/16
ST 14
ANDERSON ™
HUBBELL ® POWER SYSTEMS
FARGO ®
October 2016