Substation Connectors (Combined)
SUBSTATION TERMINALS
HUBBELL ® Power Systems
EHV WELDED EXPANSION TERMINALS FOR TUBE TO FLAT PAD TYPE EVKET
ALUMINUM EVKET
Aluminum alloy, tube to flat, compact expansion terminals are designed for corona free service at 500 KV. This design provides ±2 inch expansion. This catalog number does not include tongue mounting hardware or bolt shields; these components must be ordered separately. Contact sealant is recommended for pads after welding. Specify “H” in catalog number if Schedule 80 EHIPS tubing is to be used; example: EVKETH-40-D.
Material:
Castings – 356-T6 aluminum alloy Shunts – 1100-D aluminum alloy Shield Mounting Hardware – stainless steel
Note: To obtain pad rotated 90˚, add “V” to catalog number; (example EVKETV-40-D).
Refer to installation chart DC-9295 on page 86 for instructions.
Add suffix: “-HS” for one hardware shield, and “-HS2” for two hardware shields.
90˚ ROTATED PAD EVKETV
EHV 15
345 kV AND 500 kV LINE-TO-LINE APPLICATIONS
APPROX. WT. EA. LBS. (KG)
DIMENSIONS–INCHES (MM)
CATALOG NUMBER
ALUMINUM ♦♦ CONDUCTOR SIZE IPS
L
W
C
T
B *
14-3/4 (374.65) 15 (381.00) 15-1/4 (387.35) 15-1/2 (393.70)
18 (457.20) 18 (457.20) 21-1/2 (546.10) 21-1/2 (546.10)
4-3/4 (120.65) 5 (127.00) 5-1/4 (133.35) 5-1/2 (139.70)
3/4 (19.05) 7/8 (22.23) 1 (25.40) 1 (25.40)
18.3 (8.30) 19.9 (9.03) 24.3 (11.02) 27.6 (12.52)
EVKET34D
3-1/2
10-1/16
EVKET40D
4
10-1/16
EVKET50D
5
11-3/4
EVKET60D
6
11-3/4
♦♦ 140 ft. maximum total bus length. * Height of Corona Shield