Substation Connectors (Combined)
SUBSTATION TERMINALS
HUBBELL ® Power Systems
ALUMINUM WSTFXH-EHV
Aluminum alloy, tube-to-flat terminal, designed for corona-free EHV service, on 6 EHIPS, schedule 80 bus up to 500kV. Two bolt shields are required and included:
Material: Castings – 356-T6 aluminum alloy
Note: When mounting to unshielded equipment pad, two additional hardware shields (EVHSD) must be used to ensure corona-free performance.
Pad bolting hardware is not included. Bolt lengths depend on thickness of mating pad to be clamped.
Ampacity is 5,000 amps outdoors with 2 ft/sec cross wind and normal oxidized surface, when installed with type HTJC Inhibitor compound and the two EVHSD hardware shields provided.
EHV 10
ALUMINUM CONDUCTOR SIZE EHIPS
APPROX. WT. EA. LBS. (KG)
DIMENSIONS–INCHES (MM)
CATALOG NUMBER
A
L
T
2.37 (60.2)
8.0 (203)
1.0 (25.4)
7.5 (3.4)
WSTFXH602N4CFEHV
6
ANDERSON ™
HUBBELL ® POWER SYSTEMS
FARGO ®
October 2016
Made with FlippingBook flipbook maker