Substation Connectors (Combined)
SUBSTATION TERMINALS
HUBBELL ® Power Systems
EHV TERMINALS SHORT BARREL COMPRESSION CABLE TO FLAT
ALUMINUM ACFS
Jumper terminals are prefilled with inhibitor. Pad holes have NEMA spacing.
For use with conventional hex die tooling Available with 15, 45 or 90 degree angled pad.
Example: ACFS1196N445 for 45 deg. pad angle.
IDENTIFICATION: CONDUCTOR DIAMETER RANGE DIE SIZE, MIN PRESS SIZE DATE CODE, HPS CATALOG NO.
345 kV AND 500 kV LINE-TO-LINE APPLICATIONS
O.D. (IN) STD COND. (COMPACT / TW)
PAD DETAILS LENGTH BEFORE COMPR. (IN) BOLT HOLES WIDTH (IN)
MIN. PRESS (TONS)
NET WEIGHT LB (KG)
CATALOG NUMBER
COMPR. DIES
AAC KCMIL ACSR KCMIL (STR)
636 (30/19) 715.5 (24/7) (26/7) (30/19) 795 (45/7) (54/7) (26/7) 715.5 (30/19) 795 (45/7) (54/7) (26/7) 795 (26/7) (30/19) 954 (36/1) (45/7) (54/7) 795 (30/19) 954 (45/7) (54/7) 954 (30/19) 1033.5 (45/7) (54/7) 1113 (45/7) 1113 (54/19) 1192.5 (45/7) (54/19) 1192.5 (54/19) 1272 (45/7) (54/19) 1351.5 (45/7) 1351.5 (54/19) 1431 (45/7) (54/19) 1510.5 (45/7), 1590 (45/7) 1510.5 (54/19) 1590 (45/7) (54/19) 1780 (84/19), 1869 (68/7) 2034.5 (72/7), 2057 (76/19)
1.019 - 1.108 (0.921 - 1.010)
30AH
1.7 (.77)
ACFS1108N4 795–900
60
4
2.98 11.25
1.077 - 1.108 (0.977 - 1.108)
L727
1.108 - 1.196 (1.010 - 1.084) 1.140 - 1.196 (1.040 - 1.084) 1.203 - 1.263 (1.092 - 1.165) 1.289 - 1.340 (1.165 - 1.225) 1.338 - 1.386 (1.225 - 1.259)
954–1033.5
30AH
1.7 (.77)
ACFS1196N4
60
4
3.20 11.50
1000– 1033.5
L727
34AH L767 34AH L767 36AH L728
2.4 (1.09) 2.4 (1.09) 2.7 (1.23)
ACFS1263N4 1113–1200
60
4
3.10 11.84
ACFS1340N4 1250–1351.5
60
4
3.33 12.22
ACFS1386N4 1431
60
4
3.04 12.81
1.412 - 1.504 (1.320 - 1.358)
3.0 (1.36)
ACFS1504N4 1500–1590
38AH 60
4
3.51
13.19
EHV 7
1.504 - 1.545 (1.358 - 1.424)
40AH L735
3.7 (1.68)
ACFS1545N4 1750
60
4
3.49 13.97
1.602 - 1.700 (1.445 - 1.545)
3.9 (1.77)
ACFS1700N4 2000
42AH 100
4
3.93 14.03
2167 (72/7) 2156 (84/19) 2156 (84/19) 2312 (76/19)
1.729 - 1.762 (1.545 - 1.608) 1.762 - 1.824 (1.608 - 1.650)
4.5 (2.04) 4.5 (2.04)
ACFS1762N4 2250–2300
44AH 100
4
4.0 15.31
ACFS1824N4 2500
44AH 100
4
3.93 15.44
NOTES: 1. These terminals are also recommended for AAAC and ACAR conductors within the diameter ranges listed. 2. Terminals are pre-filled with Anderson/Fargo standard joint compound. Consult factory for terminals pre-filled with high performance, conductive-grit compound type HTJC.
ANDERSON ™
HUBBELL ® POWER SYSTEMS
FARGO ®
October 2016
Made with FlippingBook flipbook maker