TEE TAPS COMPRESSION CABLE TO CABLE - OPEN RUN AAC, ALLOY, ACAR AND ACSR CONDUCTORS (CONTINUED)
Product Data & Conductor Size
CONDUCTOR RANGE (1)
LENGTH BEFORE
RUN OR TAP CODE
MINIMUM PRESS SIZE (TONS)
NET WEIGHT LB (KG)
O.D. IN (MM) AAC SIZE KCMIL ACSR SIZE KCMIL (STR)
RUN IN (MM) TAP IN (MM)
DIE SIZE
1431 (45/7) (54/19), 1510.5 (45/7) (54/19), 1590 (45/7)
16CD 38AH
1.426 - 1.520 1590, 1600, 1700
16
21.3 (541)
8.2 (210)
60
5.30 (2.41)
17CD 40AH
1.521 - 1.615
1750, 1800, 1900
1590 (54/19), 1780
17
22.6 (575)
8.8 (223)
60
6.30 (2.86)
SC 36
2034.5 (72/7), 2057 (76/19) 2167 (72/7)
19CD 44AH 100
2000, 2250, 2300
1.630 - 1.805
19 25.3 (643)
9.8 (249)
8.90 (4.04)
–
2156 (84/19), 2312 (76/19)
19CD
NOTES: (1) These tee taps also approved application on AAAC and ACAR conductors within the diameter ranges listed. (2) Standard Hex dies not available for some sleeve & conductor combinations. If no AH die listed for conductor, use only the CD die shown.
(3) Install with Fargo type UJC or, for lowest resistance connection, type HTJC inhibitor compound. (4) Tees are EHV rated where main and tap conductors are 1.0 in. (25.4 mm) O.D. or larger.
ANDERSON ™
HUBBELL ® POWER SYSTEMS
FARGO ®
October 2016