I NTRODUCT I ON HAZARDOUS LOCATION DATA
North American Use of Equipment marked For Class/Division or Zones
Both the NEC and CE Code permit the use of Class/Division marked equipment to be used in Zone Locations and Zone marked equipment to be used in Class/Division locations. The CE Code includes Table 18 whereas the NEC currently has this information in text. (The 2023 NEC Edition is expected to add a similar table to that used in the CE Code)
CLASS/DIVISION SYSTEM
ZONE SYSTEM
AREA CLASSIFICATION
AREA CLASSIFICATION
SUITABLE EQUIPMENT
SUITABLE EQUIPMENT
CLASS I, GASSES AND VAPORS
EXPLOSIVE GAS ATMOSPHERES
Intrinsically safe, Encapsulation
IS, I.S., Exi, Exia,
ma j
Zone 0
Flameproof
da jk EPL Ga
Equipment marked
Equipment suitable for use in Zone 0 Equipment marked Class I, Division 1 Purged equipment to NFPA 496
Types X, Y
Equipment marked Class I, Division 1 Purged equipment to NFPA 496
Intrinsic safety Encapsulation
ib
Types X, Y
ma, mb
Intrinsic safety Encapsulation
IS, I.S., Exi, Exia
Flameproof
d. db
Class I, Division 1
ma j da k
Intrinsic safety Increased safety
i, ib
Flameproof
e, eb
Inherently safe optical radiation Optical system with interlock
op is, with EPL Gb** op sh, with EPL Gb**
Zone 1
Pressurized enclosure
p, px, pxb, py, pyb
Powder filling
q, qb
Liquid immersion o, ob Electrical resistance trace heating 60079-30-1, EPL Gb Inherently safe optical radiation op is, with EPL Gb** Optical system with interlock op sh, with EPL Gb** Protected optical radiation op pr, with EPL Gb** Equipment marked EPL Ga or Gb
Equipment suitable for use in Zone 0 Equipment suitable for use in Zone 1
Equipment suitable for use in Class I, Division 1 Equipment suitable for use in Zone 0 Equipment suitable for use in in Zone 1 Equipment to NFPA 496
Equipment suitable for use in Class I, Division 1 Equipment suitable for use in Class I, Division Equipment to NFPA 496
Type Z
Type Z
Type of Protection “n” (Group II)
nA, nC, nL, nR
Type of Protection “n” (Group II)
nA, nC, nL, nR
Intrinsic safety Encapsulation
ic
Intrinsic safety Encapsulation
ic
mc
mc
Flameproof
dc
Flameproof
dc
Intrinsic safety Increased safety
ic
Intrinsic safety Increased safety
ic
ec
Class I, Division 2
Zone 2
ec
Pressurized enclosure
pz, pzc
Pressurized enclosure
pz, pzc
Liquid immersion oc Electrical resistance trace heating 60079-30-1, EPL Gc Skin effect trace heating with EPL Gc** Impedance heating with EPL Gc** Inherently safe optical radiation op is, with EPL Gc** Optical system with interlock op sh, with EPL Gc* Protected optical radiation op pr, with EPL Gc** Equipment marked EPL Ga, Gb or Gc Other electrical apparatus‡
Liquid immersion oc Electrical resistance trace heating 60079-30-1, EPL Gc Skin effect trace heating with EPL Gc** Impedance heating with EPL Gc** Inherently safe optical radiation op is, with EPL Gc** Optical system with interlock op sh, with EPL Gc* Protected optical radiation op pr, with EPL Gc** Equipment marked EPL Ga, Gb or Gc Other electrical apparatus‡