Jumpers & Load Pickup Tools (2300)
Insulated Jumper Sets for 15 kV, 25kV and 35 kV All CHANCE ® Insulated Jumpers meet ASTM F 2321 Standard Specification.
Features & Applications • Used for bypassing work areas when equipment is under repair • Also used for upgrading lines and making temporary or emergency repairs • Pre-assembled for popular distribution-system voltages, 10 sets offer a choice of cable sizes • Continuous-current ratings for sets range from 200 to 400 amperes based on cable size selected • All sets include cable listed below • Ampacity ratings are based on 90°C conductor temperature at 40°C ambient • AWG size and voltage rating are embossed at 4’ intervals on EPR (ethylene-propylene) insulated jacket • Insulation and conductor screen meet and exceed ICEA-NEMA standard S-68-516 • Extra-flexible conductors are alloy-coated copper stranded rope per ASTM B-189 or B-33
• Jumper clamps feature “floating-washer” design and high-impact polyethylene handles with wide handguard flange
Ordering Information Each set includes one 12 ft. cable assembled with two crimp connectors to two jumper clamps. 15 kV Sets Style I, Type I, Class A per ASTM F 2321 Standard Specification
• Small 15kV clamp has 5-5/8" handle below handguard • Large 15 kV and 25kV clamps each has 7-1/2" handle below handguard • 35kV clamp has 8-3/8" handle below handguard
Small-Conductor Range
Catalog No. C6010163 C6010162 C6010164
Cable #2
Weight 8 lb. / 3.6 kg. 9 3 / 4 lb. / 4.4 kg. 11 1 / 4 lb. / 5 kg. 8 lb. / 3.6 kg. 9 3 / 4 lb. / 4.4 kg. 11 1 / 4 lb. / 5 kg. 15 1 / 4 lb. / 7 kg.
Min. Max. Main Line Range
#6 Sol. Cu. (0.162")
795MCM ACSR (1.14")
1/0 2/0
• NOTE: Adequate rubber gloves must be worn when installing or removing jumper clamps
Large-Conductor Range - Uses longer handle 25kV clamps
C6010171 C6010172 C6010173 C6010174
#2 1/0 2/0 4/0
#6 Sol. Cu. (0.162")
795MCM ACSR (1.14")
15 kV Jumper Cable
Size, AWG
Reference Cat. No.
Continuous Current Rating, Amperes
#2
200 260 300 400
S10043 S10044 S10045 S10046
25 kV Sets Style I, Type I, Class A per ASTM F 2321 Standard Specification
Jumpers & Load Pi ckup Tool s – 2300
1/0 2/0 4/0
#6 Sol. Cu. (0.162")
795MCM ACSR (1.14")
C6010269 C6010270
1/0 2/0
10 lb. / 4.5 kg. 11 1 / 2 lb. / 5.2 kg.
25 kV Jumper Cable
S11272 S11273
1/0 2/0
260 300
35 kV Set Style I, Type I, Class A per ASTM F 2321 Standard Specification
260 35 kV Jumper Cable
S11274
1/0
#6 Sol. Cu. (0.162")
954MCM ACSR (1.165")
C6010271 1/0 15 1 / 2 lb. / 7 kg.
Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com
Oct 2021
Page 2307
Made with FlippingBook flipbook maker