Hipotronics Product Catalog (2/24/21)
TECHNICAL SPECIFICATIONS Model #
840PL-HD 0.4 – 40kV
880PL-HD 0.4 – 80kV
Voltage Current Polarity
System Output
10mA
Negative Output, Positive Ground ± 1.5% of Reading ± 0.2% F.S.
Voltage & Current Measurement Accuracy Voltage Resolution Current Resolution Insulation Resistance Measurement Range
100V 0.1 A
10kΩ – 40GΩ 1% of scale
IR Accuracy IR Resolution Duty Cycle Dimensions (W x D x H) Input
10k
90-264VAC, 45-65Hz, 900VA 1 hour ON / 1 hour OFF
Net
20in x 14in x20in (50cm x 35cm x 51 cm) 24in x 19in x 23in (61cm x 48cm x 58cm)
Shipping
Net
78lbs (36kg) 91lbs (42kg)
Weight
Shipping
Emergency Stop
Interlock Hand-switch (optional) External Warning Lamp (optional) Interlock Foot Pedal (optional)
Visual Warning Indicators
Safety Features
External Interlock
Audible Warning Indicator
Display Interfaces
7” TFT , 800 x 480, Color Touch Screen
USB 2.0 for Memory Stick
Output Data Format Calibration Interval Languages ECCN: 3A992.A
CSV
1 year recommended
English, Spanish, Portuguese, French, German, Mandarin
HTS: 9030.39.0100
Electronic Components
High Voltage Components
Temperature -10°C … +50°C -20°C … +70°C
Humidity (r.h. non-condensing)
Temperature -10°C … +50°C -20°C … +55°C
Humidity (r.h. non-condensing)
Operation Storage
5 … 95% 5 … 95%
5 … 90% 5 … 90%
SCOPE OF SUPPLY
STANDARD OPTIONS
HHDA13-280 – 120kV rated grounding stick HH-HS-DI – Hand operated interlock switch HH-FS-DI – Foot operated interlock switch
25ft HV output cable with clamp 25ft HV return cable with clamp 25ft HV ground with clamp
HH-WARN-DI – Safety Strobe light with magnetic base
6ft input power cord
EXT-WARN-1 – One-year extended warranty
Manual and calibration certificate
22 of 81