Encyclopedia of Grounding (CA09040E)
5H Clamps
T6000819 (8.5" x .75" rated stud) PST6003644 (3.75 x .75" rated stud) Bus Bar Clamp
C6003598 Tower Clamp (consists of C6000085 and
C6002256 (threaded) PSC6003412 (drilled) C-Clamp*
C6001743 C-Clamp
C6001783 Tower Clamp
C6000197 Duckbill
Catalog Number
C6001584 combined)
Continuous Current (Amps)
400
400
400
400
400
400
Rated Fault Current 15 cycles
47kA, X/R=30
Recommended Torque (in-lb)
250
300
300
250
250
250
1000 kcmil Cu 1590 kcmil ACSR (1.50”)
3/4” x 5” Angles or Flats or 5/8” O.D. Rod
Main Line Range Maximum
4” x 4” Square 4.5” O.D. Bus
4” Structural Angles
950 kcmil Cu 1510 kcmil ACSR 2” O.D. Bus
Main Line Range Minimum
#6 Sol. Cu (0.162”)
4/0 Str. Cu. (0.500)
2” Structural Angles
#6 Solid Cu (0.162")
#6 Solid Cu (0.162")
1/8 "
Ground Cable for max clamp rating
No Cable Rated Stud
4/0
4/0
4/0
4/0
4/0
Weight
1-1/2 lb. / 0.7 kg 5.25 lb/2.4 kg 4.8 lb/2.2kg
5 lb/2.25 kg 3-3/4 lb/1.7 kg 1-1/2 lb/0.7 kg 1-3/4 lb/0.8 kg
Type I Class A (smooth jaw) Grade 5H
Type I Class A (smooth jaw) Grade 5H
Type III Class B (serrated jaw) Grade 5H
Type III Class B (serrated jaw) Grade 5H
Type I Class B (serrated jaw) Grade 5H
Type I Class B (serrated jaw) Grade 5H
ASTM Designation
*Unshrouded Ferrules Only
12-6
ENCYCLOPEDIA OF GROUNDING
Made with FlippingBook flipbook maker