Encyclopedia of Anchoring (CA06114E)

DETERMINING GUY LOADS

How To Determine The Guy Load After the line load is known, the Guy Load Reference table is used as a quick reference for determining the load on the guy at different angles of pull. Determine proper safety factor based on the National Electric Safety Code or the appropriate safety codes in your area.

Anchor Rod Strength

Nominal Rod Dia.

Ultimate Strength

⅝"

16,000 lbs.

¾"

23,000 lbs.

A

1"

36,000 lbs.

1" High Strength

50,000 lbs.