EHV Substation Connectors (AEC-16)
TECHNICAL DATA
HUBBELL ® Power Systems
TUNGSTEN - ARC
4043 FILLER ROD SIZE
WALL THICKNESS AMPERES
GAS CUP DIA. INCHES
TUNGSTEN DIA.
ARGON FLOW CFH
PREHEAT ˚F
NO. PASSES
IPS SIZE
1/2
.108
125-150
3/8
1/8
20
None
1
1/8
3/4
.113
125-150
3/8
1/8
20
None
1
1/8
1
.133
125-150
3/8
1/8
30
None
1
1/8
1-1/4
.140
160-170
3/8
1/8
30
None
1
1/8
1-1/2
.144
160-170
3/8
1/8
30
None
1
1/8
2
.154
170-190
1/8
1/8
30
None
1
3/16
2-1/2
.203
170-190
1/2
3/16
40
None
1
3/16
Optional to 400˚F Optional to 400˚F Optional to 400˚F Optional to 400˚F Optional to 400˚F Optional to 400˚F
1
3/16
3
.216
170-190
1/2
3/16
40
1
3/16
3-1/2
.226
170-190
1/2
3/16
40
1
3/16
4
.237
180-200
1/2
3/16
50
1
3/16
4-1/2
.247
180-200
1/2
3/16
50
1 or 2
3/16
5
.258
180-200
1/2
3/16
50
1 or 2
3/16
6
.280
180-200
1/2
3/16
50
FLAT BAR
4043 filler rod size
gas cup dia. inches
tungsten dia.
argon flow cfh
preheat ˚F
no. passes
FLAT bar thickness amperes
1/8
125
3/8
1/8
30
None
1
1/8
1/4
150
1/2
3/16
30
None
1
3/16
Optional to 400˚F
1
1/4
3/8
300
1/2
3/16
50
1/2
400
5/8
1/4
50
400˚F
1 or 2
1/4
3/4
450
5/8
1/4
50
400˚F
2
5/16
1
500
5/8
5/16
50
400˚F
2
5/16
95
™
Made with FlippingBook - Online catalogs