EC&M Crane Control Class 9998

Animated publication

Crane Control Class 9998

Catalog 03

CRANE CONTROL CLASS 9998

CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page DC Coil Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Replacement Parts Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155

Crane Control Class 9998 DC Coil Data

DC COIL DATA FOR CLASS 7001 TYPE K RELAYS DC operating coils are designed in accordance with NEMA Standards to withstand 110% of rated voltage continuously and to operate the contactor successfully at 80% of rated voltage.

Standard DC Operating Coils for Class 7001 Type K Relays

Full Shunt Coils

Class 7001 Device

Coil Resistance Ohms @ 20 ° C ✝

Coil Amperes @ 20 ° C ✝

Coil Number

VDC

Type

5101706750

300

2050

0.146

5101705650

230-240

1619

0.148

5101706752

190

863

0.222

5101706753

150

547

0.274

5101705651

115-120

415

0.294

5101706755

100

226

0.442

KG, KE, KF

5101706756

75

140

0.536

5101706757

60

87

0.690

5101706758

45

57

0.789

5101706759

36

36

1.000

5101706760

24

12.8

1.880

5101706761

12

3.5

3.43

Half Shunt Coils

Devices Using Coil

Coil Amperes @ 20 ° C ✝

Coil Resistance Ohms @ 20 ° C ✝

Coil Number

VDC

Type

5115204450

230-240

1828

0.131

KF

5115204451

115-120

477

0.252

✝ At normal operating temperature the coil resistance will increase by approximately 20% Price Information – Consult EC&M.

CRANE CONTROL CLASS 9998

152

© 2003 The Electric Controller & Mfg. Co., LLC All Rights Reserved

09/03

Crane Control Class 9998 DC Coil Data

DC COIL DATA FOR CLASS 7001 TYPE K RELAYS

Full Series Coils

Class 7001 Device

Coil Resistance Ohms @ 20 ° C ✝

Coil Amperes @ 20 ° C ✝

Coil Number

Type

5115207750 5115207751 5115207752 5115207753 5115207754 5115207755 5115207756 5115207757 5115207758 5115207759 5115207760 5115207761 5115207762 5115207763 5115207764 5115207850 5115207851 5115207852 5115207853 5115207854 5115207855 5115207856 5115207857 5115207858 5115207902 5115207903 5115207904

177 110

0.39 0.49 0.62 0.77 0.97

71.2 45.6 28.6 16.6 10.4

1.2 1.6 2.0 2.4 3.1 3.8 4.9 6.1 7.3 9.9

6.67 4.46 2.76 1.78 1.08 0.69 0.43 0.27

KI, KF

– – – – – – – – – – – –

12.5 16.0 20.8 26.6 35.2 45.3 58.0 75.6

114.5 171.5 257.5 200.0

Half Series Coils

Devices Using Coil

Coil Amperes @ 20 ° C ✝

Coil Resistance Ohms @ 20 ° C ✝

Coil Number

Type

5115203650 5115203651 5115203652 5115203653 5115203654 5115203655 5115203301 5115203302 5115203303

– – – – – – – – –

7.36

11.71 18.75 29.45 46.90 73.60

KI, KF

114.5 171.5 257.5

CRANE CONTROL CLASS 9998

Coils with External Diode Devices Using Coil

Coil Ohms @ 20 ° C ✝

Coil Amps @ 20 ° C ✝

ReverseOhms ● @ 20 ° C ✝

Coil Number ▲

System Volts Coil Volts

Type

5101705651

240

120

407

0.294

1MEG

KP

5101705659

120

60

107

0.561

1MEG

▲ Does not include external diode. Diode P/N is 5122902950. ● Reverse ohms can only be measured when externally mounted diode is in series with coil. ✝ At normal operating temperature the coil resistance will increase by approximately 20%. Price Information – Consult EC&M.

153

© 2003 The Electric Controller & Mfg. Co., LLC All Rights Reserved

09/03

Crane Control Class 9998 DC Coil Data

DC COIL DATA FOR CLASS 7004 AND 8503 TYPE M CONTACTORS DC operating coils are designed in accordance with NEMA Standards to withstand 110% of rated voltage continuously and to operate the contactor successfully at 80% of rated voltage.

Standard DC Operating Coils for Class 7004 and 8503 Type M Contactors

Class 7004 and 8503 Device

Coil Resistance Ohms @ 20 ° C ✝

Coil Part Number 5101505654 5101505650 5101505655 5101505656 5101505651 5101505657 5101505658 5101505659 5101505660 5101505661 5101505662 5101505663 5101705654 5101705650 5101705655 5101705656 5101705651 5101705657 5101705658 5101705659 5101705660 5101705661 5101705662 5101705663 5101924352 5101924353 5101924354 5101924355 5101924356 5101924357 5101924358 5101924359 5101924360 5101924361 5101924362 5101924363 5102024352 5102024353 5102024354 5102024355 5102024356 5102024357 5102024358 5102024359 5102024360 5102024361 5102024362 5102024363 5102205670 5102205671 5102205672 5102205673 5102205674 5102205675 5102205676 5102205677 5102205678 5102205679 5102205680 5102205681

Coil Amperes @ 20 ° C ✝

VDC

Size

Type

Poles

300

3910 2133 1515

0.077 0.113 0.125 0.160 0.196 0.252 0.292 0.361 0.437 0.554 0.873 0.110 0.140 0.167 0.212 0.289 0.321 0.414 0.492 0.692 0.800 0.153 0.194 0.237 0.288 0.381 0.413 0.547 0.674 1.63 1.22 2.31

230-240

190 150

940 613 397 257 166 103

115-120

100

MXCO1, MXDO1 MXCO3, MXDO3

SPNO SPNC

1 & 2

75 60 45 36 24 12

65

27.5

7.35

300

2734 1712 1135

230-240

190 150

706 415 312 181 122

115-120

100

MEO1, MFO1 MEO3, MFO3

SPNO SPNC

3 & 4

75 60 45 36 24 12

65 45

19.7

5.20

300

1960 1240

230-240

190 150

801 520 315 242 137

115-120

100

MGAO1, MGO1 MGAO3, MGO3

SPNO SPNC

5 & 5A

75 60 45 36 24 12

89 45 31

1.00 1.16 1.66 3.08

14.5

3.9

300

1097

0.273 0.333 0.433 0.528 0.678 0.877

230-240

720 439 284 177 114

190 150

115-120

100

MHAO1, MHO1 MHO3

SPNO SPNC

6 & 6A

75 60 45 36 24 12

74

1.01 1.42 1.64 2.02 3.54 6.63

42.3 27.5 17.8

6.78 1.81

CRANE CONTROL CLASS 9998

300

639 401 259 159

0.469 0.599 0.734 0.943

230-240

190 150

115-120

94 61

1.28 1.64 1.98 2.50 2.96 3.64 4.00 8.57

100

MJO1, MKO1 MJO3, MKO3

SPNO SPNC

7 & 8

75 60 45 36 24 12

37.9 24.0 15.2

9.9 6.0 1.4

✝ At normal operating temperature the coil resistance will increase by approximately 20%

154

© 2003 The Electric Controller & Mfg. Co., LLC All Rights Reserved

09/03

Crane Control Class 9998 Replacement Parts Kits

Price Information – Refer to “Repair Parts Price List,” or consult your Local Square D Field Office.

FOR MAGNET CONTROLLERS AND AC AND DC TYPE M AND MX CONTACTORS Copper contact tips are standard. Silver-faced contact tips are available and are recommended for applications where the contactors remain closed for long periods of time. Silver-faced contact tips are standard on crane manual-magnetic disconnect switches and are optional on DC starters. Each kit contains movable and stationary contacts, necessary hardware and servicing instructions.

Copper Contact Tips

Equipment to be Maintained

Number of Poles in Kit

Parts Kit Type

Price

Contactor Size

Class

Type

$ 257.

AD-01 through AD-04 (2-19 A)

...

MA1

248.

AD-13 through AD-16 (19-130 A)

...

MA2

6815 Magnet Controllers

122.

SD-20 through SD-29 (2-30 A)

...

MA3

122.

SD-30 through SD-39 (31-80 A)

...

MA4

183.

SD-40 through SD-49 (81-130 A)

...

MA5

129.

MX

1 & 2

2

MX1

273.

MX

3

2

MX3

105.

M

3

2

ME1

7004 DC Contactors and 8503 AC Contactors

117.

M

4

2

MF1

153.

M

5 & 5A

2

MG1

309.

M

6 & 6A

2

MH1

534.

M

7 & 8

2

MJK1

▲ Each kit contains complete set of parts to change contacts on both “Lift” and “Drop” contactors.

Silver Contact Tips

Equipment to be Maintained

Number of Poles in Kit

Parts Kit Type

Price

Contactor Size

Class

Type

$ 714.

MX

1 & 2

2

MX2

1149.

M

3

2

ME2

7004 DC Contactors and 8503 AC Contactors

1188.

M

4

2

MF2

1662.

M

5 & 5A

2

MG2

1995.

M

6 & 6A

2

MH2

3324.

M

7 & 8

2

MJK2

Ordering Information Required:

1. Class 2. Type

CRANE CONTROL CLASS 9998

Discount Schedule

CP9C

155

© 2003 The Electric Controller & Mfg. Co., LLC All Rights Reserved

09/03

Made with FlippingBook PDF to HTML5