EC&M Crane Control Class 7004

Crane Control Class 7004 Type M Line-Arc® DC Contactors

APPLICATION DATA

Class 9999 AI1 Arc Suppressor The Class 9999 AI1 arc suppressor is designed to reduce arcing of pilot devices in DC inductive control circuits of 250 VDC or less.

Type

Price

360 .

AI1

The AI1 arc suppressor will limit the inductive voltage surge to a maximum of 600 VDC when applied in accordance with the application chart. When applying the arc suppressor to a circuit, two factors must be considered, the current drawn by the inductive load and the number of times per minute that the load will be interrupted. Once these two factors are determined, the application is checked against the application chart. The chart shows the maximum interruptions per minute that the arc suppressor can handle at a given current. As long as an application falls below the curve, the arc suppressor will handle the load. The arc suppressor is connected in parallel with the inductive load and is in the circuit at all times.

Class 9999 Type AI1 Arc Suppress

Application Chart for AI1 Arc Suppressor

60

50

40

30

L = 11H

20

PER MINUTE

10

L = 20H

CURRENT IN AMPERES PERMISSIBLE INTERRUPTIONS 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4

CRANE CONTROL CLASS 7004

Approximate Dimensions And Weights

Clearance for (2) 1/4" mtg. screws

111 4.38

1.65 3.00

42 76

3.75

95

0.25

6.3

1.00

25

1.93

49

2.25

mm Dual Dimensions: inches

57

Net Weight – 1 lb (0.45 kg)

Ordering Information Required:

1. Class 9999 2. Type AI1

113

© 2003 The Electric Controller & Mfg. Co., LLC All Rights Reserved

1/17

Made with FlippingBook Learn more on our blog