Distribution Connectors (Combined)

Overhead Primary Taps Hot Line Tap Clamps Aluminum

ALUMINUM S1500A

• For Aluminum and ACSR conductor. • Designed for standard hot stick application.

Material:

Body and Keeper – Aluminum Alloy Eyebolt – Bronze Alloy – Tin Plated Eyestem – Bronze Alloy, Forged or Stainless Steel Spring (on eyestem) – Stainless Steel

DC-1

W

D

Options: “AA” suffix - For no tin plating

“AGP” suffix - For tin plated part, replace AA with AGP “AC” suffix - For Aluminum/Copper bimetallic washer in eyebolt, replace AA with AC (available for S1530 only) Replace Prefix “S” with “P” - For factory greased and bagged part (i.e. P1534AGP)

H

FIGURE 1

FIGURE 2

FIGURE 3

Product Data & Conductor Size

CONDUCTOR RANGE AWG (IN.) [MM]

EYEBOLT

STANDARD PACK

CATALOG NUMBER

FIG NO.

WIDTH IN. (MM)

DEPTH IN. (MM)

HEIGHT IN. (MM)

MAIN

TAP

HARD WARE SIZE

WRE NCH SIZE

CARTON WEIGHT LBS. (KG)

AN GLE

QTY

ACSR

AAC

ACSR AAC & CU

#8 - 2/0 (0.128 -

#6 - 2/0 (0.184 - 0.419) [4.67 - 10.64] #6 - 400 (0.184 - 0.728) [4.67 - 18.49] #6 - 400 (0.184 - 0.728) [4.67 - 18.49] 4/0 - 795 (0.528 - 1.028) [13.41 - 26.11]

#8 - 1/0 (0.158 - 0.398) [4.00 - 10.11] #6 - 3/0 (0.198 - 0.502) [5.00 - 12.75] #6 - 3/0 (0.198 - 0.502) [5.00 - 12.75] #6 - 266.8 (0.198 - 0.642) [5.00 - 16.31] #6 - 266.8 (0.198 - 0.642) [5.00 - 16.31] #8 - 397.5 (0.158 - 0.743) [4.00 - 18.87]

#8 - 1/0 (0.158 - 0.398) [4.00 - 10.11]

1.750 (44.45)

2.800 (71.12)

5.250 (133.35)

40.000 (18.14)

15 o

0.419) [3.25 - 10.64]

S1520AA 1

3/8 9/16

100

#6 - 397.5 (18/1)

#6 - 4/0 (0.162 - 0.528) [4.11 - 13.41] #6 - 4/0 (0.162 - 0.528) [4.11 - 13.41]

2.400 (60.96)

2.400 (60.96)

7.130 (181.10)

32.000 (14.51)

60 o

S1530AA 2

7/16 11/16

50

(0.198 - 0.743) [5.00 - 18.87]

#6 - 397.5 (18/1)

2.400 (60.96)

2.400 (60.96)

7.130 (181.10)

32.000 (14.51)

60 o

S1534AGP 2

7/16 3/4

50

(0.198 - 0.743) [5.00 - 18.87]

#4 - 350 (0.232 -

3/0 (6/1) - 636 (30/19) (0.502 - 1.019) [12.75 - 25.88] 556.5 (30/7) - 1510 (45/7) (0.953 - 1.466) [24.21 - 37.24]

3.000 (76.20)

3.000 (76.20)

7.750 (196.85)

49.000 (22.23)

60 o

0.681) [5.89 - 17.30]

S1540AA 2

1/2

3/4

50

700 - 1590 (0.964 - 1.454) [24.49 - 36.93]

#4 - 350 (0.232 -

3.000 (76.20)

3.700 (93.98)

9.630 (244.60)

27.000 (12.25)

60 o

S1545AA 2

0.681) [5.89 - 17.30]

1/2

3/4

20

#4 - 477 (0.232 -

18 o (No Eye bolt)

#3 - 477 (0.260 - 0.795) [6.60 - 20.19]

#4 - 397.5 (0.257 - 0.743) [6.53 - 18.87]

3.63 (92.20)

7.750 (196.85)

44.000 (19.96)

2.600 (66.04)

S1535AA 3

0.795) [5.89 - 20.19]

50

1/2

3/4

In accordance with ANSI C119.4, the ampacity limitation for a hotline tap clamp is the maximum amperage of the largest tap conductor for which the clamp is rated. This ampacity should be in accordance with the conductor manufacturers recommended maximum ampacity of that conductor size.

800.346.3062 | hubbellpowersystems.com |