Distribution Connectors (Combined)

Deadends Bolted Quadrant Strain Clamp Aluminum

ALUMINUM PG / DE

DA-14

For distribution and light transmission construction with all aluminum, ACSR or aluminum alloy conductor.

Material:

Body and Keeper – 356-T6 Aluminum Alloy Hardware – Galvanized Steel Sockets and Clevises – Ductile Iron, Galvanized Cotter Pin – #302 Stainless Steel

DIMENSIONS INCHES (MM)

CATALOG NUMBER

L

W

H

K

3-7/8” (98.30) 4-1/16" (103.18) 5-1/2" (139.7) 6-7/16" (163.51) 6-9/16" (166.69) 9-7/8” (250.83)

11/16" (17.46) 11/16" (17.46) 11/16" (17.46) 25/32" (19.84) 1-1/16" (26.99) 1-3/16" (30.16)

3-13/16" (96.84) 4-3/4" (120.65) 5-5/16" (134.87) 7” (177.80) 7-7/16” (188.91) 9-5/16" (236.54)

7/8” (22.10) 1” (25.40) 1” (25.40) 1-1/8" (28.58) 1” (25.40) 1-1/4" (31.75)

DE46

PG46

PG57

PG70

PG86L

PG100L

Product Data

CLAMPING RANGE

ULTIMATE BODY STRENGTH LBS. (kN)

U-BOLTS

APPROX. WT. EACH LBS. (KG)

CATALOG NUMBER

GROOVE ANGLE

SIZE INCHES (MM)

ACSR

ALUMINUM INCHES (MM)

NO.

#6 (6/1) To 3/0 (6/1) #6 (6/1) To 3/0 (6/1) #4 (6/1) To 4/0 (6/1)

#6 -7 Str. To 3/0-19 Str. #6 -7 Str. To 3/0-19 Str. #3-7 Str. To 4/0-19 Str. 3/0-7 Str. To 400-37 Str. 4/0-7 Str. To 556.5-37 Str. 4/0-7 Str. To 750-61 Str.

0.18” - 0.52” (4.57 - 13.21)

8,000 (35.59)

1/2” (12.70)

1.2 (0.54 )

DE46N

1

85°

0.18” - 0.52” (4.57 - 13.21)

8,000 (35.59)

3/8” (9.53)

1.1 (0.50)

2

90°

PG46N**

0.25” - 0.57” (6.35 - 14.48)

10,000 (44.48)

1/2” (12.70)

2.0 (0.91)

2

90°

PG57N**

101.8 (12/7) To 336.4 (26/7) 134.6 (12/7) To 556.5 (18/1) 3/0 (6/1) To 666.6 (24/7)

0.46” - 0.73” (11.68 - 18.54)

15,000 (66.72)

1/2” (12.70)

2.5 (1.13)

2

85°

PG70N

0.52” - 0.88” (13.21 - 22.35)

15,000 (66.72)

1/2” (12.70)

2.9 (1.32)

2

70°

PG86LN

0.50” - 1.00” (12.70 - 25.40)

18,000 (80.07)

1/2” (12.70)

4.5 (2.04)

2

60°

PG100LN

NOTES: Rated slip strength as a percentage of conductor RBS varies with conductor type, size and stranding. Minimum slip strength rating on standard strength conductors is 40% RBS (Partial Tension per ANSI C119.4). Consult factory for slip strength test data on specific clamp and conductor combinations. Add Suffix “C” for Clevis Fitting (Type CA) Add Suffix “S” for Socket Eye Fitting (Type SA) ** RUS Listed

| hubbellpowersystems.com | 800.346.3062