Tap & Stirrup Clamps (DC) - Distribution Connectors
OVERHEAD PRIMARY TAPS HOT LINE CONNECTORS TWO HOLE PAD BRONZE AND ALUMINUM
BRONZE BHF/AHF
• Wide body contact area and two hole pad tap provide high cur- rent transfer for jumper or hot line clamp application. • BHF—Bronze protected thread hot line clamp with two hole NEMA pad. Designed for copper main to copper flat pad tap.
Material:
Casting — BHF/GH1010 – Bronze Alloy BHF—FTP – Bronze Tin Plated AHF – Aluminum Alloy Spring (on Eyestem) – Stainless Steel Eyestem – Bronze
DC 11
AHF – Aluminum protected thread hot line clamp with two hole NEMA pad. Designed for aluminum main to aluminum flat pad tap.
FIGURE 1
FIGURE 2
FIGURE 1
Product Data & Conductor Size
CONDUCTOR RANGE (KCML)
DIMENSIONS INCHES (MM)
APPROX. WT. EACH LBS. (KG)
CATALOG NUMBER FIG. NO.
MAIN
MATERIAL
A MAIN CONTACT WIDTH H
6 Sol. - 500 Str. CU .162” - .813”
1.5 (36.75)
1.375 (35.0) 1.375 (35.0)
6.75 (171.4)
1.66 (.75) 1.52 (.69)
BHF500B2
1
Bronze
6 Sol – 400 CU .160 - .730
5.125 (130.25)
GH1010
2
Bronze
–
ANDERSON ™
HUBBELL ® POWER SYSTEMS
FARGO ®
December 2014