DESIGN EXAMPLES

Distance Along Nail Behind Wall Face (ft)

GOLDNAIL STRENGTH ENVELOPE FIGURE 8-17

Maximum allowable moment at midspan (Step 9) is 566 ft∙lb/ft, therefore:

Determine allowable shear using Equation 8-55

EQUATION 8-55

EQUATION 8-53

V N

= 0.125 √ f’ c h c = 0.125 √ 4 (4) = 1000 lb/lf

FS Mc = (566 / 327) = 1.73 OK Check shear force at cantilever (S c ) using Equation 8-54. EQUATION 8-54 S c = K a [ g (H 1 2 / 2) + qH 1 ] = 0.33 [ 120 (3 2 / 2) + 100 (3) ] = 277 lb/ft

EQUATION 8-56

FS shear = (1000 / 277) = 3.6 OK

DESIGN EXAMPLE 11: HELICAL PILES/ANCHORS FOR TELECOMMUNICATION TOWERS

PURPOSE This Design Example provides an aid in the selection of appro priate helical guywire anchors and center mast helical piles for telecommunication towers. The guywire loads are to be resisted by a helical tension anchor. When the vertical and horizontal components are provided the resultant must be determined as well as the angle between the resultant load and the horizontal, (this is the angle the heli cal anchor should be installed at to properly resist the guywire load(s)). There may be one or more guywires that come to the ground to be restrained by one or more helical anchors de pending on the magnitude of the load and/or the soil strength. Helical piles can be used to resist the loads from the structure

mast. These loads will generally be composed of a vertical load and a lateral load at the base of the mast or pole. If the structure is a self supporting tower (SST), the loads from each leg of the tower must be resisted. These generally consist of vertical uplift and compression loads and a horizontal shear load at the ground line. These three loads can be dealt with in a number of ways. Typically one or more helical piles are used for each leg of the tower and may be installed at a batter to better resist the horizontal shear loads. Steel grillages and reinforced concrete caps have been used to facilitate load transfer from the structure to the helical piles. This type design will not be covered in this design example since the intent is to focus on the guyed mast tower structure.