CanadianConnectors (CA05041E )
Ampacity Ratings of Anderson&Fargo
Heavy Duty (1) Bolted Pad Connectors Compression, Welded and Close-Fit Bolted Designs
Product Data and Conductor Size
BoltedPad
Bolts (2)
Ampacity (A) (4)
Dimensions (in)
InhibitorType
Width
Length
Number
Size (in)
Standard
HTJC (3)
1.5
3.0
2
0.5
1220
1400
2.0
3.0
2
0.5
1260
1450
3.0
3.0
4
0.5
2450
2825
4.0
4.0
4
0.5
2580
3000
6.0
4.0
6
0.5
3825
4400
NOTES: (1) Heavy duty connectors are defined as having continuous cross section about the periphery of the conductor and through the pad, equal to or greater than 125% of the conductor. (2) Ratings assume use of steel clamping bolts and Belleville spring washers. Higher ampacity ratings can be achieved if conductive bolts, nuts and washers are used. (3) HTJC is the Anderson/FARGO conductive grit joint compound, recommended for maximum conductivity in compression and bolted pad joints. (4) Ratings are based on conductor temperature of 90°C in 40°C ambient, 2 ft/sec. cross wind.