CanadianConnectors (CA05041E )
EHV Jumper Support, 2-Bundle Conductor 3” Post (Horizontal) Insulator Assembly, 230kV - 345kV
ASSEMBLY TAJ21PCVN
Jumper Clamp Assembly
Catalog Number
Clamp Range
12.00
273838-3001CVN
1.00-1.40 Diameter
Ø14.00
R.47
273839-3001CVN
1.40-1.60 Diameter
Ø7.00
8.06
273840-3001CVN
1.60-2.00 Diameter
Ø8.00
ø .94
JLC24818357CVN
2.00-2.48 Diameter
1.31
Gain Base Pole Diameter Range
Section Length
1
18.00
14.00
12˚
3
2
Base Assembly Bill of Material
Item Part Number
Description
Quantity
Material
UBS lb
1
See Chart
Insulator, Post w/Ring
1
Polymer
—
2
See Chart
Jumper Clamp Assembly
1
Steel/Aluminum
5,000
3
See Note 1
Armor Rods
2
Aluminum
—
Typical Insulator Selection
Line Voltage (kV)
Quadri*Sil® Part Number
Section Length Inches
RCL lb
Corona Ring
230
P300074S002A
85.6
1,740
15” Line End
345
P300099S002A
110.4
1,315
15”Line End
NOTE: RCL is 50% of the ultimate cantilever load capacity. Maximum design tension load rating is 12,500 lb. For quoting/ordering instructions, see Assemblies section. (1) See Armor Rod section for rod set based on conductor application. (2) Jumper Clamp Assembly with “CVN” suffix will come with hardware galvanized per CSA G164.
©2017 Hubbell Incorporated | hubbellpowersystems.com