Cable Accessories (C7)
35KV DEADBREAK STACKING DIMENSIONS
The diagram below shows typical Cable Accessories combinations and includes the dimensions for each part as they pertain to this diagram. Choose a desired combination and add up the dimensions of each part to obtain the distance the complete unit would extend from the equipment face plate. Example: A 600 A Standoff Bushing with a 600 A T-Body and a 35kV Elbow Tap Plug and a 35 kV Elbow Arrester would have a stacking dimension of 20.64 inches (5.20 + 0.50 + 10.77 + 4.17).
35 kV Standoff Bushing 635SB
35 kV Basic Insulating Plug 635BIP
6.85
5.20
35 kV Small interface Elbow Tap Plug 635ETP
35 kV Grounding Bushing 635GB
4.17
0.50
35 kV Bushing Extender 635BE
35 kV Small Interface Elbow Arrester 235ELAxx
5.72
10.77
600A Deadbreak Junction W/U-Strap 635JxU
35 kV Small interface Loadbreak Reducing Tap Plug 635LRTP
4.26
35 kV Small Interface Insulating Cap 235IC
6.89
10.77
35 kV Connecting Plug 635CP
4.35
600A Deadbreak Junction W/Bracket 635JxB
35 kV Insulating Cap 635IC
10.01
9.56
35 kV T-Body 635TB
0.50
35 kV T-Body 635TB
35 kV Integral Bushing
4.90
6.85
35 kV Basic Insulating Cap 635BIP
5.08
0.50
4.90
35 kV Deadbreak Elbow Arrester 635EDAxx
35 kV Deadbreak Elbow Arrester 635EDAxx