H - 2200 - Conductor Supp

Crossarm Conductor Support

For use during replacement of poles or repair/replacement of pole top and stand-off insulators

• • •

Working Load Limit: 150 lb. (68 kg) per wireholder Side Load Working Load Limit 100 lb. (45 kg) Can be installed with a Grip-All clampstick

Catalog Number

Product Name

Weight

C4000517

Temporary Crossarm Conductor Suport

5.75 lb., 2.6 kg

Insulator should be installed if the tool is left in place overnight Clamps to the crossarm, adjusting to crossarms from 3.25 in x 4 in (82 mm x 101 mm) to 6 in x 6 in (152 mm x 152 mm) For 34.5kV or when the tool is left overnight, an M48057 insulator should be installed.

H - 2200 - Conductor Supp

Pole-Mounted Conductor Support

For use during replacement of poles or repair/replacement of pole top and stand-off insulators. Features wheel tightener for poles up to 14 in (355 mm) diameter Tested per ASTM F711 Rated at 15kV Phase to Phase, 34.5kV Phase to Phase with M48057 insulators (sold separately) added to each wireholder H4809W has 30 in (762 mm) spacing pole to wireholder C4001509 has 48 in (1.2 m) long Epoxiglas arm • • • • •

Catalog Number

Product Name

Weight

H4809W

Temporary Single Conductor Support

17.5 lb., 7.9 kg

C4001509

Temporary Two Conductor Support

26.5 lb., 12.0 kg