CA01082E_Catalog 30
Products – High Strength Polymer Housed Surge Arresters – SVNH & SVNX
SVNH Physical Characteristics
Recommended Minimum Clearance - Inches (mm)
Creepage Distance - Inches (mm) 184 (4676) 184 (4676) 184 (4676) 225 (5704) 225 (5704) 285 (7230) 285 (7230) 285 (7230) 285 (7230) 326 (8291) 326 (8291) 326 (8291) 449 (11408) 469 (11913) 469 (11913)
Total Height - Inches (mm) 68.9 (1750) 68.9 (1750) 68.9 (1750) 78.8 (2001) 78.8 (2001) 112 (2856) 112 (2856) 112 (2856) 112 (2856) 122 (3108) 122 (3108) 122 (3108) 152 (3862) 176 (4470) 176 (4470)
Net Weight - Pounds (kg)
Drawing Figure
Standard Arrester Catalog Number
Duty Cycle Rating (kV)
MCOV (kV)
Phase to Ground 25.1 (638) 28.8 (732) 30.9 (785) 31.8 (808) 33.6 (853) 42.5 (1080) 46.9 (1191) 47.6 (1209) 49.4 (1255) 51.7 (1313) 52.9 (1344) 55.2 (1402) 72.1 (1831) 76.1 (1933) 80.2 (2037)
Phase to Phase 28.9 (734) 33.1 (841) 35.4 (899) 36.5 (927) 38.6 (980) 48.5 (1232) 53.5 (1359) 54.3 (1379) 56.4 (1433) 59.0 (1499) 60.3 (1532) 62.9 (1598) 82.1 (2085) 86.5 (2197) 91.2 (2316)
SVNH144GA115AA SVNH168GA131AA SVNH172GA140AA SVNH180GA144AA SVNH192GA152AA SVNH240GA190AA SVNH258GA209AA SVNH264GA212AA SVNH276GA220AA SVNH288GA230AA SVNH294GA235AA SVNH312GA245AA SVNH396GA318AA SVNH420GA335AA SVNH444GA353AA
144 168 172 180 192 240 258 264 276 288 294 312 396 420 444
115 131 140 144 152 190 209 212 220 230 235 245 318 335 353
346 (157) 350 (159) 353 (160) 401 (182) 404 (184) 607 (276) 614 (279) 615 (280) 617 (280) 651 (296) 652 (296) 656 (298) 828 (376) 993 (451) 998 (454)
1 1 1 2 2 3 3 3 3 3 3 3 3 4 4
These arresters are typically applied to system voltages higher than 500 kV where the energy require ments are higher than required for lower voltage systems. If a high energy rated arrester is required for a lower system voltage, Hubbell Power Systems can provide these. Please contact your Hubbell Power Systems Representative at 1.573.682.5521 for more information.
SVNX Physical Characteristics
Recommended Minimum Clearance - Inches (mm)
Creepage Distance - Inches (mm)
Total Height - Inches (mm)
Net Weight - Pounds (kg)
Drawing Figure
Standard Arrester Catalog Number
Duty Cycle Rating (kV)
MCOV (kV)
Phase to Ground
Phase to Phase
SVNX396GA318AA SVNX420GA335AA SVNX444GA353AA SVNX588GA470AA
396 420 444 588
318 335 353 470
449 (11408) 469 (11913) 469 (11913) 736 (18694)
152 (3862) 176 (4470) 176 (4470) 259 (6579)
67.0 (1702) 71.0 (1803) 75.0 (1905) 100 (2540)
77.0 (1956) 81.0 (2057) 85.0 (2159) 114 (2896)
1080 (491) 1285 (584) 1294 (588) 1847 (840)
3 4 4 5
Page 34 | October 2023