CA01082E_Catalog 30

Products – High Strength Polymer Housed Surge Arresters – SVNH & SVNX

SVNH Physical Characteristics

Recommended Minimum Clearance - Inches (mm)

Creepage Distance - Inches (mm) 184 (4676) 184 (4676) 184 (4676) 225 (5704) 225 (5704) 285 (7230) 285 (7230) 285 (7230) 285 (7230) 326 (8291) 326 (8291) 326 (8291) 449 (11408) 469 (11913) 469 (11913)

Total Height - Inches (mm) 68.9 (1750) 68.9 (1750) 68.9 (1750) 78.8 (2001) 78.8 (2001) 112 (2856) 112 (2856) 112 (2856) 112 (2856) 122 (3108) 122 (3108) 122 (3108) 152 (3862) 176 (4470) 176 (4470)

Net Weight - Pounds (kg)

Drawing Figure

Standard Arrester Catalog Number

Duty Cycle Rating (kV)

MCOV (kV)

Phase to Ground 25.1 (638) 28.8 (732) 30.9 (785) 31.8 (808) 33.6 (853) 42.5 (1080) 46.9 (1191) 47.6 (1209) 49.4 (1255) 51.7 (1313) 52.9 (1344) 55.2 (1402) 72.1 (1831) 76.1 (1933) 80.2 (2037)

Phase to Phase 28.9 (734) 33.1 (841) 35.4 (899) 36.5 (927) 38.6 (980) 48.5 (1232) 53.5 (1359) 54.3 (1379) 56.4 (1433) 59.0 (1499) 60.3 (1532) 62.9 (1598) 82.1 (2085) 86.5 (2197) 91.2 (2316)

SVNH144GA115AA SVNH168GA131AA SVNH172GA140AA SVNH180GA144AA SVNH192GA152AA SVNH240GA190AA SVNH258GA209AA SVNH264GA212AA SVNH276GA220AA SVNH288GA230AA SVNH294GA235AA SVNH312GA245AA SVNH396GA318AA SVNH420GA335AA SVNH444GA353AA

144 168 172 180 192 240 258 264 276 288 294 312 396 420 444

115 131 140 144 152 190 209 212 220 230 235 245 318 335 353

346 (157) 350 (159) 353 (160) 401 (182) 404 (184) 607 (276) 614 (279) 615 (280) 617 (280) 651 (296) 652 (296) 656 (298) 828 (376) 993 (451) 998 (454)

1 1 1 2 2 3 3 3 3 3 3 3 3 4 4

These arresters are typically applied to system voltages higher than 500 kV where the energy require ments are higher than required for lower voltage systems. If a high energy rated arrester is required for a lower system voltage, Hubbell Power Systems can provide these. Please contact your Hubbell Power Systems Representative at 1.573.682.5521 for more information.

SVNX Physical Characteristics

Recommended Minimum Clearance - Inches (mm)

Creepage Distance - Inches (mm)

Total Height - Inches (mm)

Net Weight - Pounds (kg)

Drawing Figure

Standard Arrester Catalog Number

Duty Cycle Rating (kV)

MCOV (kV)

Phase to Ground

Phase to Phase

SVNX396GA318AA SVNX420GA335AA SVNX444GA353AA SVNX588GA470AA

396 420 444 588

318 335 353 470

449 (11408) 469 (11913) 469 (11913) 736 (18694)

152 (3862) 176 (4470) 176 (4470) 259 (6579)

67.0 (1702) 71.0 (1803) 75.0 (1905) 100 (2540)

77.0 (1956) 81.0 (2057) 85.0 (2159) 114 (2896)

1080 (491) 1285 (584) 1294 (588) 1847 (840)

3 4 4 5

Page 34 | October 2023

Made with FlippingBook flipbook maker