ARRESTERS
Routine Testing
Hubbell performs routine acceptance testing on 100% of arresters manufactured. Testing is done in accordance with IEEE C62.11 and IEC 60099-4 surge arrester standards. Additional testing is performed in accordance with internal Hubbell design specifications. If required, please contact your Hubbell representative for a copy of the routine arrester test certification. After assembly, the arresters are 100% tested as follows: Residual (Discharge) Voltage: Determined by the sum of the MOV elements, each arrester is certified to be within a manufacturer specified range that aligns with the arrester’s published ratings. Reference Voltage: The voltage at which the arrester conducts the reference current per the table below. This test verifies the proper MOV blocks were used in the assembly.
PDV-65 Optima
3 mA
PDV-100 Optima
4 mA
PVR Optima
5 mA
PVI-LP
7 mA
Partial Discharge (PD): Power-frequency voltage is raised to the duty cycle voltage rating of the arrester, held for not less than 2s, and then lowered to 1.05 times the MCOV of the arrester. The measured PD shall not exceed 10 pC. Power Frequency (PF): A minimum voltage of 1.25 times the MCOV of the arrester is applied to verify that the measured values of watts loss does not exceed the arrester or unit’s specified limits.
Mechanical Capability
Distribution arresters rarely see mechanical loading outside of forces exerted during installation or sporadic wind gusts. Each Hubbell product line has distinct mechanical capabilities based on IEEE and IEC standards, as well as Hubbell internal specifications. The following values are conservative in nature and are in excess of common application requirements.
Maximum Design
Specified Long Term Load (SLL) - in-lbs (Nm)
Specified Short Term Load (SSL) - in-lbs (Nm)
Tension - lbf (kN)
Torsion - in-lbs (Nm)
Compression - lbf (kN)
Product Line
Cantilever Load (MDCL) - in-lbs (Nm)
PDV-65 Optima
300 (34)
300 (34)
600 (68)
562 (2.5)
239 (27)
562 (2.5)
PDV-100 Optima
700 (79)
700 (79)
1200 (135)
562 (2.5)
239 (27)
562 (2.5)
PVR Optima
1200 (135)
-
-
562 (2.5)
478 (54)
562 (2.5)
PVI-LP
1130 (128)
1130 (128)
2260 (256)
562 (2.5)
478 (54)
562 (2.5)
*MDCL confirmed by IEEE C62.11, SLL/SSL confirmed by IEC 60099-4