EBAC Bushing - Technical Product Brochure (EC-2)

Draw Lead or Solid Connect Terminal Options

Draw Lead: • Connector can be designed for brazed or crimped configuration • Available in 400A draw-lead or 400/1200A interchangeable with bottom connect terminal • Bushing can be used with or without a bottom terminal

Fixed Copper Connector: • Lower end is supplied with different options such as NEMA blades or standard thread

   Capacitance Tap

• The flange is made of machined high strength aluminum with a leak-proof seal between the bushing and the equipment • The test tap is integrated into the mounting flange • Capacitance taps come standard with transformer bushings; optional for breaker bushings • Ground shield connection is provided by a solid welded pin attachment • Shield positioning is optimized using electrostatic field calculation software

  Bushing Name Plate

• Each bushing is routine tested for partial discharge, power factor, capacitance and dry withstand (hi-pot) • A detailed routine test report is provided with each bushing (100% testing and reporting) • A name plate is attached to the bushing flange providing information to the field personnel