Small Terminals

General Information

Performance The terminals and splices in this catalog are approved, per SAE-AS7928 and/or UL486, where indicated. Table 1 shows the performance requirements for terminals used in military and commercial equipment. The voltage drops listed are maximum allowable values taken at currents well above rated current for the wires. Tensile values assure that the wires will not become separated from the terminals under reasonably expected stresses. UL tensile values are chosen to reflect the severest expected duty. MIL Specification tensile values apply only to crimp terminations and reflect minimum values that are obtained in good crimp joints. Actual performance of BURNDY terminals exceeds the requirements of Table 1. Typical values are shown in Figures 1-5. For High Temperature applications BURNDY ® YAV series with nickel plating “-NK” suffix provide for continuous operation to 650 ° F and 750 ° F intermittent service.

Table 1

Performance Requirements — Terminals for Copper Wire

Per SAE-AS7928

Per UL 486

Max. Voltage

Min. Tensile Strength (lbs)

Min. Tensile Strength (lbs)

Test Current For Max. 50 ° C Rise (Amps)

Wire Size

Test Current (Amps)

Drop (Mv.)

26 24 22 20 19 18 14 12 13

3

8 8 7 6 5 7 6 5 5 5 5 5 5 5 5 5 5 5

7

— —

— — — — — — 15 20 30 50 65 85

4.5

10 15 19 38 50 70

9

8

11 16 22 32 41 55 73

13 20 30 50 70 80 90

110 150 225 300 400 550 650 700 750 825 875

8 6 4 2 1

101 135 181 211 245 283 320 380

100 140 180 200 250 300 350 450

115 130 150 175 200 230

1/0 2/0 3/0 4/0

Fig. 2. Tensile strength of BA VINYLUG™ after axial rotation stresses.

Fig. 1. Tensile strength of YAD HYLUG™ after axial rotation stresses.

TENSILE STRENGTH IN POUNDS

TENSILE STRENGTH IN POUNDS

COMMERCIAL WIRE SIZE

COMMERCIAL WIRE SIZE