BURNDY Master Catalog (20190422)
Mechanical
U-BLOK™Mounting Platforms for Trough Applications
U-BLOK™MOUNTING PLATFORMS
For Trough Applications
Catalog Number TBPT6 TBPT8 TBPT10 TBPT12
Gutter Size
W
L
H
Weight Each (lb)
4-1/4 4-1/4 4-1/4 4-1/4
5-7/8 7-7/8 9-7/8 11-7/8
1-1/2 3-1/2
6 '
3/4
8 "
1-1/4 1-1/2 1-3/4
4 4
10 " 12 "
Hole pattern shown is for reference only.
ALLOWABLE AMPACITIES OF INSULATED CONDUCTOR, 60° TO 90° C **
Copper
Al or Copper Clad Al
Size AWG kcmil
60 deg. C
75 deg. C
90 deg. C
60 deg. C
75 deg. C
90 deg. C
12 10
25 30 40 55 70 85 95
25 35 50 65 85
30 40 55 75 95
20 25 30 40 55 65 75 85
20 30 40 50 65 75 90
25 35 45 60 75 85
8 6 4 3 2 1
100 115 130 150 175 200 230 255 285 310 335 380 420 460 475
110 130 150 170 195 225 260 290 320 350 380 430 475 520 535
100 115 135 150 175 205 230 255 280 305 350 385 420 435
110 125 145 165 195 215 240 260 280 320 355 385 400
100 120 135 155 180 205 230 250 270 310 340 375 385
1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750
100 115 130 150 170 190 210 225 260 285 310 320
** NOTE : Values referenced from Article 310 of the National Electric Code, Table 310-16, 1996. The above chart is to be used for REFERENCE ONLY. Please consult Table 310-16 of the National Electric Code (latest revision) for information regarding insulation type, voltage range, and conductor housings/surroundings. U-TAP™, U-BLOK™, and SPEC-BLOK™ connectors are rated for 90 deg. C by Underwriters’ Laboratories. Use of 60 deg. C and 75 deg. C conductor(s) is valid, though only as determined by the National Electric Code.
1-800-387-6487 (Canada) 1-603-647-5299 (International)
A-61
Made with FlippingBook - Online Brochure Maker