Mechanical Grounding
BONDIT ® Wall Mounted Intersystem Bonding Connector Type BDTIBB, BONDIT ® Wall Mounted Intersystem Bonding Connector
NEC 250.94 refers to a requirement in the 2008 National Electrical Code. In the past, gorund wires from telephone systems or cable systems were allowed to be grounded separately from the GEC (Ground Electrode Conductor from the main electrical service). With the new code, all ground wires from separate systems such as telephone systems, CATV and radio systems must be tied together at one location to the GEC. Hence, the term intersystem refers to tying all of the “system” grounds together in one location. The BONDIT ® - Wall Mount is a great solution when the GEC is exposed (not in conduit). With the new BONDIT ® - Wall Mount connector BURNDY provides an economical solution that meets the needs of NEC 250.94. Catalog Number: BDTIBB
Satellite Dish
Intersystem Ground Wire (Ex.: Telephone)
Conductor Range
Reference Dimensions
Catalog Number
Lay-In Section
Conductor Ports
L
W H
M
Ground Conductor (GEC)
3.99 [101]
0.71 [18]
0.91 [23]
2.46 [62]
BDTIBB
#6 - #2 AWG
#14 - #4 AWG
Features & Benefits •
Meets Intersystem Bonding Requirements; NEC 250.94 • Provides an easy to access grounding point for utilities such as telecom and cable • Easy to install • UL Listed and CSA Certified • Tin-plated connector body provides long-lasting corrosion resistance •
Stainless steel set screws
• Accepts main ground wire (#2 to #6), up to (4) intersystem wire (#4 to #14) • Supplied with a durable cover, easily secured over connector body • Approved for use with solid stranded conductors
STAINLESS STEEL SCREW
STAINLESS STEEL SCREW (4 PLACES)