BURNDY Master Catalog (20190422)

Compression Grounding

HYGROUND ® Compression System HYTAP™ Type YGHHC-C Double Figure C Connector

HYTAP™ Type YGHHC-C Double Figure C Connector

IEEE-837 2014 Qualified!

Irreversible compression ground tap figure “C” connectors. Accommodates all cable combinations from #6 solid through 500 kcmil. “C”- shaped opening permits placing two continuous parallel cables into conductor groove. The YGHHC-C series is qualified to IEEE-837 2014. Prefilled with PENETROX™compound and strip sealed.

Commercial Copper Cable toCable or Cable toGroundRod

InstallationData

StrandedCopper CableRangeMetric

Die Index No.

No. of Crimps

Catalog Number

H L Z

Y750/Y35/ PAT750/Y39

Y45

Y46

Run

Tap

Run

Tap

3

4

35mm² (7.62mm) 70mm² (10.9mm) 95mm² (12.5mm) 120mm² (14.4mm) 95mm² (12.5mm) 120mm² (14.4mm) 150mm² (16mm) 240mm² (20.35mm) 150mm² (16mm) 240mm² (20.35mm) 150mm² (16mm) 240mm² (20.35mm)

35mm² (7.62mm) 70mm² (10.9mm) 10mm² (4.10mm) 70mm² (10.90mm) 95mm² (12.5mm) 120mm² (14.4mm) 10mm² (4.10mm) 70mm² (10.90mm) 95mm² (12.5mm) 120mm² (14.4mm) 150mm² (16mm) 240mm² (20.35mm)

1 Str. (0.328) 2/0 Str. (0.419) 3/8" Rod

1 Str. (0.328) 2/0 Str. (0.419)

1.54 [39]

0.75 [19]

1.88 [48]

YGHHC26C26

O U-O U-O U-O 2

3/0 Str. (0.470) 250 kcmil (0.575) 1/2" or 5/8" Rod    3/0 Str. (0.470) 250 kcmil (0.575) 1/2" or 5/8" Rod 300 kcmil (0.630) 500 kcmil (0.813) 3/4" Rod

6 Sol. (0.162) 2/0 Str. (0.419)

1.97 [50]

0.88 [22]

2.13 [54]

YGHHC29C26

997

U997

U997

U997

2

3/0 Str. (0.470) 250 kcmil (0.575)

2.06 [52]

0.88 [22]

2.13 [54]

YGHHC29C29

997

U997

U997

U997

2

6 Sol. (0.162) 2/0 Str. (0.419)

2.42 [62]

0.88 [22]

2.13 [54] 1011 U1011

YGHHC34C26

S1011 P1011

4

6

YGHHC34C29 6

300 kcmil (0.630) 500 kcmil (0.813)

3/0 Str. (0.470) 250 kcmil (0.575)

2.67 [68]

0.88 [22]

2.13 [54] 1011 U1011

S1011 P1011

4

YGHHC34C34 300 kcmil (0.630) 500 kcmil (0.813)

300 kcmil (0.630) 500 kcmil (0.813)

2.91 [74]

1.10 [28]

2.58 [66] 1011 U1011

S1011 P1011

6

6

For ground rod to wire applications, ground rod must be precrimped; see table for appropriate precrimp dies Where a “U” or “PU” die is recommended with the Y45 HYPRESS™, a PT6515 adapter must be used Where a “U” or “PU” die is recommended with the Y46 HYPRESS™, a PUADP-1 adapter must be used

These connectors cannot be installed with the Y35 or Y39 HYPRESS™

2

6

Ground Rod Dia.

PRECRIMP Dies

3

UPRECRIMP 12 UPRECRIMP 58 UPRECRIMP 34

1/2" 5/8" 3/4"

4

U2CABT

1-800-387-6487 (Canada) 1-603-647-5299 (International)

E-11