BURNDY Master Catalog (20190422)

Compression Connections

Aluminum / Copper —One Hole Uninsulated Aluminum Terminals

TYPES YA-A, YA-A-TN (Continued)

AL9CU NOTE: Field bending straight lugs to achieve an angular connection will void UL Listing / CSA Certifications and BURNDY will not be liable for the connection.

Dimensions

Installation Tooling▲

No. of Holes in Pad

Dieless (# of crimps)

Y35, Y39, Y750, Y46*

Wire Strip Length

Catalog Number

Code Conductor

Stud Size

▲Die Index

DieNum- ber (# of crimps)

C D L N T Z

Mechanical Tooling

Hydraulic HYPRESS™

Color Code

600 kcmil 500 kcmil CCADLO (779/22) *900 Compact AL 700 - 750 kcmil 900 kcmil Class B Compact Only 600 kcmil CCADLO (925/22) 900 kcmil AL600 kcmil CU 800 kcmil 1000 kcmil 750 kcmil CCADLO (1194/22) 800 kcmil CCADLO (1258/22)

U36ART (4)

YA36A1

5/8

1

1.97 1.88 5.82 0.88 0.52 1.00

— Y / PAT644 (1) Y / PAT81KFT (4)

Black 473 2 7/8

YA39A1 YA39A3

1/2 5/8

1 1

2.05 1.34 5.26 0.63 0.43 0.71 2.05 1.88 5.80 0.88 0.43 1.00

U39ART-2 (4)

— Y / PAT644 (1) Y / PAT81KFT (4)

Yellow 936 2 7/8

YA39A34

3/4

1

2.05 2.19 6.17 1.00 0.43 1.19

YA42A1 YA42A3

1/2 5/8

1 1

2.14 1.36 5.32 0.63 0.39 0.71 2.14 1.36 5.32 0.66 0.39 1.00

U42ART (4)^

— Y / PAT644 (2)

Gray 303 2 7/8

YA44A1

5/8

1

2.50 1.89 6.50 0.88 0.66 1.01

— P44ART** (4)

Brown 302

3

• Contact BURNDY ® for conductor, stud sizes and hole drillings not shown. ▲ See tooling section of this catalog for complete tool and die listings. No color code assigned. ‡ UL Listed for Aluminum only. 1

* Use PUADP-1 adaptor with U dies in Y46 Hypress™. ♦ For applications greater than 2000 Volts consult cable manufacturer for voltage stress relief instructions. Note: All dimensions shown are for reference only.

1-800-387-6487 (Canada) 1-603-647-5299 (International)

C-199