BURNDY Master Catalog (20190422)
Compression Connections
Copper Compression — Flex — Two Hole Narrow Tongue, Standard Barrel —with Inspection Window
TYPE YAV-L-2NT-FX (Continued)
Straight
45°
90°
NOTE: Field bending straight lugs to achieve an angular connection will void UL Listing / CSA Certifications and BURNDY will not be liable for the connection.
FigureDimen- sions
Conductor
Installation Tooling
Stud Hole Size
Stud Hole Spacing
Mech.
Hydraulic
Wire Strip Length
Tongue Width
CatalogNumber
Y35, Y39, Y750 Y46*, PAT750
AWG/ KCMIL
MM² ***
Dieless (# of crimps)
Color Code
Die Index
MD6, OUR840, MD7-34R
(B) (T) (L)
BCT500, Y500CT
300kcmil G,H,I,K,M DLO313 (775/24) 350kcmil G,H,I,K,M DLO373 (925/24) 500kcmil G,H DLO444 (110/24) 500kcmil H,I,K 550kcmil G,H,I DLO535 (1325/24) DLO646 (1600/24) 750kcmil G,H DLO777 (1925/24) 929kcmil DLO (2300/24) 650 kcmilG
W31VT (2) W31RT (2)
U31RT (2)
Y /PAT644(1) Y /PAT81KFT(1)
YA32L2NT38FX
185 3/8 1.00"
0.96 1.19 0.20 3.69
W31VT (2)
Red 18 1-1/4
W32VT (2) W32RT (2)
U32RT (2)
Y /PAT644(1) Y /PAT81KFT(1) Y /PAT644(1) Y /PAT81KFT(1) Y /PAT644(1) Y /PAT81KFT(1) Y /PAT644(1) Y /PAT81KFT(1) Y /PAT644(1) Y /PAT81KFT(1) Y /PAT644(1) Y /PAT81KFT(1) Y /PAT644(1) Y /PAT81KFT(2)
YA34L2NT38FX
240 3/8
1
0.96 1.27 0.23 3.88
W32VT (2)
Blue 19 or
470 1-5/16
YA36L2NT38FX
— 3/8 1.00"
1.63 1.38 0.27 4.24
—
— U34RT (2) — U34RT (2) — U38XRT (2) — U38XRT (2) — U38XRT (2)
Brown 20
YA36L2ENT38E10FX
— 3/8 1.25 1.50 1.38 0.27 4.49
—
YA38L2ENT38FX
300 3/8 1.00"
1.50 1.45 0.27 4.35
—
1-7/16
YA38L2NT38FX
300 3/8
1
1.63 1.45 0.27 4.35
—
Pink L99
YA38L2NNTFX
300 1/2 1.75 1.63 1.45 0.27 5.35
—
YA40L2NNTFX
400 1/2 1.75 1.63 1.42 0.30 5.38
—
— U39RT (2)
Black 24 1-5/16
YA44L2NNTFX
1/2 1.75 1.63 1.65 0.33 5.74
U44XRT (2) •P44XRT (2)
Y /PAT644(1) Y /PAT81KFT(2)
500
—
—
Yellow L115 1-5/8
YA44L2NT38FX
3/8
1
1.63 1.65 0.33 4.74
YA45L2NT38FX
— 3/8 1.00"
1.70 2.00 0.38 5.18
—
— P44RT (2)
White 27 2-1/16
—
Consult cable manufacturers for stress relief instructions ♦ For applications greater than 2000 Volts consult cable manufacturer for voltage stress relief instructions * Use PUADP-1 adaptor with U dies in Y46 HYPRESS™ • P-RT dies for Y / PAT46 Tooling only
*** The MM 2 conductor sizes Listed are the recommendations for CLASS 5 conductor
▲See tooling section of this catalog for complete tool and die listings. Use ONLY color-coded die recommendations for -FX connectors Note: All dimensions shown are for reference only
www.burndy.com 1-800-346-4175 (US)
C-74
Made with FlippingBook - Online Brochure Maker