BURNDY Master Catalog (20190422)
Compression Connections
Copper Compression — Code — Two Hole Narrow Tongue, Long Barrel — No Inspection Window
TYPE YA-2NT (Continued)
Straight
45°
90°
NOTE: Field bending straight lugs to achieve an angular connection will void UL Listing / CSA Certifications and BURNDY will not be liable for the connection.
▲ InstallationTooling
Conductor
FigureDimensions
Mechanical
Hydraulic
Stud Hole Spac- ing
Stud Hole Size
MD6, OUR840, MD7-34R
Y35,Y39 Y750,Y46* PAT750
Wire Strip Length
Catalog Number
*** MM²
Tongue Width
Dieless (#ofcrimps)
BCT500HS, Y500CTHS
Color Code
Die Index
AWG
(B)
(T)
(L)
MY29-3(2) MY29-11(2) MRC840(4) Y644HSXT(1) Y81KFT(1) Y81KFTMBH(1) PAT81KFT-18V(1) MY29-3(2) MY29-11(2) MRC840(4) Y644HSXT(1) Y81KFT(2) Y81KFTMBH(2) PAT81KFT-18V(2) MY29-3(2) MY29-11(2) MRC840(4) Y644HSXT(1) Y81KFT(2) Y81KFTMBH(2) PAT81KFT-18V(2) MY29-3(2) MY29-11(2) MRC840(4) Y644HSXT(1) Y81KFT(2) Y81KFTMBH(2) PAT81KFT-18V(2) MY29-3(2) MY29-11(2) Y644HSXT(1) Y81KFT(2) Y81KFTMBH(2) PAT81KFT-18V(2) Y644HSXT(1) Y81KFT(3) Y81KFTMBH(3) PAT81KFT-18V(3)
YA252NT14
1/4″
5/8″
0.48″
1.38″ 0.09″ 3.05″
W25VT(4) W25RT(4) X25RT(4)
W25VT(4) W25RT(4) X25RT(4)
YA252NT14E1
1/4″
1″
0.48″
1.38″ 0.09″ 3.05″
U25CRT(2) U2CABT(2)
1/0AWG 53.5
Pink
12
1-7/16″
YA252NT38
3/8″
1″
0.48″
1.38″ 0.09″ 3.05″
YA262NT14
1/4″
5/8″
0.48″
1.50″ 0.12″ 3.22″
YA262NT14E1
1/4″
1″
0.48″
1.50″ 0.12″ 3.59″
W26VT(4) W26RT(4) X26RT(4)
W26VT(4) W26RT(4) X26RT(4)
2/0AWG 67.4 70
U26RT(2)
Black
13
1-9/16″
YA262NT516
5/16″
1″
0.52″
1.50″ 0.13″ 3.66″
YA262NT38
3/8″
1″
0.62″
1.50″ 0.13″ 3.78″
YA272NT14
1/4″
5/8″
0.60″
1.50″ 0.13″ 3.26″
W27VT(4) W27RT(4) X27RT(6)
W27VT(4) W27RT(4) X27RT(6)
YA272NT516
5/16″
1″
0.60″
1.50″ 0.13″ 3.70″
3/0AWG 85
U27RT(2)
Orange 14
1-9/16″
YA272NT38
3/8”
1″
0.76″
1.50″ 0.13″ 3.82″
YA282NT14
1/4″
5/8”
0.76″
1.62” 0.14” 3.42”
W28VT(4) W28RT(4) X28RT(6)
W28VT(4) W28RT(4) X28RT(6)
YA282NT516
5/16″
1″
0.76″
1.62” 0.14” 3.86”
4/0AWG 107
U28RT(2)
Purple
15 1-11/16″
YA282NT38
3/8”
1″
0.76″
1.62” 0.10” 3.99”
YA292NT14
1/4″
5/8″
0.76″
1.62″ 0.16″ 3.49″
YA292NT516 YA292NT38
5/16″
1″ 1″
0.76″ 0.76″ 0.76″
1.62″ 0.16″ 3.90″ 1.62″ 0.16″ 4.02″ 1.62″ 0.16″ 4.77″
W29VT(4) W29RT(4) X29RT(8)
W29VT(4) X29RT(8)
250kcmil
127
U29RT(2)
Yellow 16 1-11/16″
3/8″ 3/8″
YA292NT38E16
1-3/4″
YA292NNT
1/2″
1-3/4″
0.96″
1.62″ 0.16″ 5.21″
17 or 298
152 150 3/8″
W30VT(4) W30RT(4)
U30RT(4) U28ART(4)
YA302NT38
300kcmil
1″
0.52″
2.00″ 0.13″ 3.66″
W30VT(4)
White
2-1/16”
▲See tooling section of this catalog for complete tool and die listings. Use ONLY color-coded die recommendations for -FX connectors. For nest/indentor system contact factory.
♦ For applications greater than 2000 Volts consult cable manufacturer for voltage stress relief instructions. Note: All dimensions shown are for reference only.
* Use PUADP-1 adapter with U dies in Y46 HYPRESS™ *** The MM 2 conductor sizes listed are the recommendations for Class 2 conductor
1-800-387-6487 (Canada) 1-603-647-5299 (International)
C-41
Made with FlippingBook - Online Brochure Maker