BURNDY Master Catalog (20190422)

Compression Connections

Copper Compression — Code —One Hole Long Barrel —with Inspection Window

TYPE YAZ (Continued)

Straight

45°

90°

NOTE: Field bending straight lugs to achieve an angular connection will void UL Listing / CSA Certifications and BURNDY will not be liable for the connection.

FigureDimen- sions

Conductor

Installation Tooling

Stud Hole Size

Mech.

Hydraulic

Wire Strip Length

Catalog Number

Tongue Width

Y35, Y39, Y750 Y46, PAT750 U36RT (4) U32ART (4)

Dieless (# of crimps)

Color Code

Die Index

MD6, OUR840, MD7-34R

AWG MM² ***

(B)

(T)

(L)

BCT500HS, Y500CTHS

YAZ36TC38 YAZ36TC12

3/8 1.74 2.69 0.26 4.54 1/2 1.74 2.69 0.26 4.60

600 kcmil 304 300

Green 22 or

472 2-3/4

YAZ37TC12 650 kcmil

— 1/2 1.80 2.81 0.27 4.75

U37RT (4) Orange 23 2-7/8

YAZ38TC12 700 kcmil 355 1/2 1.84 2.81 0.27 4.77

U38RT (4)

Pink 400 2-7/8

YAZ39TC38 YAZ39NT12 YAZ39TC12

3/8 1.91 2.88 0.27 4.81 1/2 1.63 2.88 0.27 4.87 1/2 1.91 2.88 0.27 4.87

Y644HSXT (1) Y81KFT (4) Y81KFTMBH (4) PAT81KFT-18V (4)

U39RT (4) P39RT** (4)

750 kcmil 380

Black 24 2-15/16

YAZ40TC12 800 kcmil 405

— Orange 25

3

400 1/2 1.98 2.94 0.30 4.94 — 1/2 2.01 2.94 0.31 4.96

YAZ41TC12 YAZ44TC38 YAZ44TC12

850 kcmil

— Gold 26

3

3/8 2.19 3.00 0.33 5.08 1/2 2.19 3.00 0.33 5.14

1000 kcmil 1250 kcmil 1300 kcmil 1500 kcmil 1750 kcmil 2000 kcmil

507 500

P44RT** (4) P45RT** (6)

White 27 3-1/16

YAZ45TC12

633 1/2 2.46 3.19 0.38 5.43

Yellow 29 3-1/4

YAZ453TC12

— 1/2 2.53 3.19 0.39 5.46

— Orange 30 3-1/4

P46RT** (6)

YAZ46TC12

760 1/2 2.69 3.19 0.40 5.53

Green 31 3-1/4

YAZ47TC12

887 1/2 2.90 3.44 0.42 5.87

— Gray 33 3-1/2

YAZ48TC12

1010 1/2 3.10 3.44 0.46 5.95

— Brown 34 3-1/2

† The MM 2 conductor size listed is for Class 2 and Class 5 conductor ▲ See tooling section of this catalog for complete   tool and die listings • Available undrilled. Add suffix U to catalog  number (example: YA25U)

* Use PUADP-1 adapter with U dies in Y46   HYPRESS™ ** P-RT die sets for use in Y46 HYPRESS™ only, PUADP-1 adapter not required *** The MM 2 conductor sizes listed are the recommendations for Class 2 conductor

♦ For applications greater than 2000 Volts consult cable manufacturer for voltage stress relief instructions Note: All dimensions shown are for reference only

www.burndy.com 1-800-346-4175 (US)

C-28