BRYANT 2021 Full Line Catalog (BC003 1/21)

Hospital Grade Devices

Healthcare Outlet Assemblies (HCOA)

UL2930 Listed

• First UL2930 Product Ever Sold • 15A and 20A 125V Versions • 6 ft. or 15 ft. Cord Length • Surge Protected Models in all Configurations • #12/3 AWG Cord

Surge Protection Plug Strips

UL2930 Health Care Outlet Assembly (HCOA)

Six

Number of Outlets

1100

Joule Rating

30 kA $2,500

Peak AMP Rating

Down Line Warranty

Length

6 Foot

15 Foot

15A BRY6MG6 20A BRY6MG620 15A BRY6MGRPT6 20A BRY6MGRPT620

BRY6MG15

UL 2930 HCOA with L-N Surge Protection, White UL 2930 HCOA Relocatable Power Tap (RPT), White

BRY6MG1520 BRY6MGRPT15 BRY6MGRPT1520

UL2930 Healthcare Outlet Assembly (HCOA) BRY6MG Series

Product Dimensions Inches (mm) Non-Metallic Strips

BRY6MGRPT Series

Metallic Strips

SPD and Power Strip

SPD w/ Fax/Modem CATV/Satelite

SPD and Power Strip

SPD with Fax Modem

Electrical Specifications Current Voltage Frequency Surge Component

15A 125V 60Hz MOV

20A 125V 60Hz MOV

15A 125V 60Hz N/A

20A 125V 60Hz N/A

A B C

11.2" (284.5) 14.75" (374.7) 10.4" (264.2)

12.25" (311.2)

2.36" (59.9) 1.85" (47.0)

2.36" (59.9) 1.85" (47.0)

3.8" (96.5) 1.44" (36.6)

2.5" (63.5) 1.5" (38.1)

EQUIPMENT GROUNDING TERMINAL

Performance UL VPR L-N

600V N/A -11 dB to -68 dB (10kHz to 100MHZ) 3kA

L-G, N-G EMI Noise Filtration:

2.22 [56.4]

11.90 [302.3]

In (Nominal Discharge Current) MCOV Peak Current Rating L-N

N/A

12 AWG POWER CORD WITH MOLDED HOSPITAL GRADE PLUG

150V 30KA <1mA 550j

.32 [8.1]

1.92 [48.7]

Leakage Current: Total Joules (L-N)

BRY6MGRPT6 SHOWN.

Environmental Specifications Operating Temperature

-40°F to 160°F (-40°C to 70°C)

 .25 [6.4]

UL 2930; UL File # E488399; RoHs Compliant; NFPA 99 2012 ed; ANSI / IEEE Category A (HBL6MG Series Only)

Certifications

8.32 [211.3]

B-10

www.hubbell.com/bryant/en/

Specifications are subject to change without notice.

Made with FlippingBook Digital Proposal Maker