Jumpers & Load Pickup Tools (2300)
Insulated By-Pass Jumpers • Rated for 15 kV phase-to-phase systems
Jumpers & Load Pi ckup Tool s – 2300
Features & Applications • Center support for easy application • Available in four jumper-cable sizes • Features mid-span orange 8’-long epoxy-resin, fiberglass reinforced-plastic (FRP) tube • Rigid 1-1/2”-O.D. tube serves as a support for easy handling of jumper set by rubber gloves or hot-line tools • This makes the unit especially handy when jumpering switchgear, reclosers or cutting in double deadends • Completely pre-assembled • Two non-metallic hangers – one at each end of the FRP support tube • These hangers provide for parking the by-pass clamps while moving the jumper set into or out of the work area since the 16’-long jumper cable (with EPR jacket) is secured where it exits the FRP tube, 4’ of cable extend from both ends of the rigid support • Threaded compression assemblies – each comprising a connector, nut and lockwasher, all of copper – are applied at the cable ends • Two clamps (each a CHANCE C6001743) also come installed with cable strain-relief clamps to complete the by-pass jumper set
Insulated Jumper Sets Each: 16-ft. overall length (includes 8-ft. tube) with two C6001743 clamps applied on cable by copper connector assemblies Ordering Information
• Aluminum body with smooth jaws • Bronze eyescrew with fine threads Clamp Specifications Recommended Torque 250 inch-pounds Main Line Range:
Catalog Number C6010260 C6010261 C6010262 C6010263
Cable Size, AWG #2 – 15kV 1/0 – 15kV 2/0 – 15kV 4/0 – 15kV
Continuous Current Rating
Weight (lb./kg.)
Minimum Maximum
#6 Solid Copper (0.162") 1590 kcmil ACSR (1.5")
200 amperes 260 amperes 300 amperes 400 amperes
27/12.15 29/13.05 32/14.4 37/16.65
Terminal threads 5 / 8 "-11 UNC
(plus cable strain-relief clamps)
Oct 2021 Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com
Page 2308